Summary of Contents for Endress+Hauser Proline 500 HART
Page 1
Products Solutions Services KA01312D/06/EN/01.17 71376054 Brief Operating Instructions Proline 500 HART Transmitter with electromagnetic sensor These instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Transmitter Brief Operating Instructions Contain information about the transmitter. Sensor Brief Operating Instructions →...
Page 2
Proline 500 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Page 3
These Brief Operating Instructions are the Transmitter Brief Operating Instructions. The "Sensor Brief Operating Instructions" are available via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App Detailed information about the device can be found in the Operating Instructions and the other documentation: • Internet: www.endress.com/deviceviewer...
Proline 500 HART Document information Document information Symbols used 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in WARNING serious or fatal injury.
Page 6
Document information Proline 500 HART Symbol Meaning Protective Earth (PE) A terminal which must be connected to ground prior to establishing any other connections. The ground terminals are situated inside and outside the device: • Inner ground terminal: Connects the protectiv earth to the mains supply.
Proline 500 HART Basic safety instructions Basic safety instructions Requirements for the personnel The personnel must fulfill the following requirements for its tasks: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣ Are authorized by the plant owner/operator.
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
Proline 500 HART Basic safety instructions Device-specific IT security The device offers a range of specific functions to support protective measures on the operator' s side. These functions can be configured by the user and guarantee greater in-operation safety if used correctly.
Product description Proline 500 HART Product description The measuring system consists of a Proline 500 transmitter and an electromagnetic Proline Promag sensor. The transmitter and sensor are mounted in physically separate locations. They are interconnected via two connecting cable. Transmitter with integrated ISEM (intelligent sensor electronics module)
Proline 500 HART Installation Installation For detailed information about mounting the sensor, see the Sensor Brief Operating Instructions → 3 Mounting the transmitter housing CAUTION Ambient temperature too high! Danger of electronics overheating and housing deformation. ‣ Do not exceed the permitted maximum ambient temperature .
Page 12
Installation Proline 500 HART 4.1.2 Post mounting WARNING Order code for "Transmitter housing", option L "Cast, stainless": cast transmitters are very heavy. They are unstable if they are not mounted on a secure, fixed post. ‣ Only mount the transmitter on a secure, fixed post on a stable surface.
Proline 500 HART Installation Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned. – – 3 mm 4 mm A0029993 Depending on the device version: Loosen the securing clamp of the connection compartment cover.
Installation Proline 500 HART Turning the display module The display module can be turned to optimize display readability and operability. – – – 3 mm A0030035 Depending on the device version: Loosen the securing clamp of the connection compartment cover.
Proline 500 HART Installation Cover locking NOTICE Order code "Transmitter housing", option L "Cast, stainless": The covers of the transmitter housing are provided with a borehole to lock the cover. The cover can be locked using screws and a chain or cable provided by the customer.
Installation Proline 500 HART Transmitter post-installation check The post-installation check must always be performed after the following tasks: • Mounting the transmitter housing: – Post mounting – Wall mounting • Turning the transmitter housing • Turning the display module Is the device undamaged (visual inspection)? ...
Proline 500 HART Electrical connection Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
Page 18
Electrical connection Proline 500 HART Signal cable Current output 4 to 20 mA HART A shielded cable is recommended. Observe grounding concept of the plant. Current output 0/4 to 20 mA Standard installation cable is sufficient. Pulse/frequency/switch output Standard installation cable is sufficient.
Page 19
Proline 500 HART Electrical connection Cable length (max.) Depends on the medium conductivity, max. 200 m (656 ft) Cable lengths (available for 5 m (15 ft), 10 m (32 ft), 20 m (65 ft) or variable length up to max. 200 m (656 ft)
Page 21
Proline 500 HART Electrical connection In the case of the coil current cable: Insulate one core of the three-core cable at the level of the core reinforcement. You only require two cores for the connection. For cables with fine-wire cores (stranded cables): Fit the cores with ferrules.
Page 22
Electrical connection Proline 500 HART Sensor Electrode cable Coil current cable 70 (2.76) 80 (3.15) 17 (0.67) 40(1.57) 8 (0.31) 8 (0.31) ≥ 1 (0.04) A0029438 A0029439 Engineering unit mm (in) A = Terminate the cable B = Fit ferrules on cables with fine-wire cores (stranded cables) 1 = Red ferrules, ...
Page 23
Proline 500 HART Electrical connection Preparing the connecting cable: Promag P and Promag W Transmitter Electrode cable Coil current cable (3.54) 100 (3.94)* 70 (2.76) 80 (3.15) 50 (1.97) 17 (0.67) 50 (1.97) 8 (0.3) 10 (0.4) 8 (0.3) A0029329...
Proline 500 HART Electrical connection Connecting the measuring device NOTICE Limitation of electrical safety due to incorrect connection! ‣ Have electrical connection work carried out by appropriately trained specialists only. ‣ Observe applicable federal/national installation codes and regulations. ‣ Comply with local workplace safety regulations.
Page 26
Electrical connection Proline 500 HART Proline Promag P and Promag W E2 S2 42 41 36 37 n.c. n.c. n.c. 42 41 E1 E2 A0029145 Coil current cable Signal cable Connecting the connecting cable to the sensor connection housing Connection via terminals with order code for "Housing"...
Page 27
Proline 500 HART Electrical connection Connecting the sensor connection housing via terminals 10 (0.4) 3 mm 22 mm 24 mm A0029612 Loosen the securing clamp of the housing cover. Unscrew the housing cover. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
Page 28
Electrical connection Proline 500 HART Connecting the sensor connection housing via terminals 10 (0.4) 8 mm 22 mm 24 mm A0029617 Release the securing screw of the housing cover. Open the housing cover. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
Page 29
Proline 500 HART Electrical connection Connecting the connecting cable to the transmitter 10 (0.4) 3 mm 22 mm 24 mm A0029592 Loosen the securing clamp of the connection compartment cover. Unscrew the connection compartment cover. Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing ring from the cable entry.
Page 30
Electrical connection Proline 500 HART 5.2.2 Connecting the signal cable and the supply voltage cable A0026781 Terminal connection for supply voltage Terminal connection for signal transmission, input/output Terminal connection for signal transmission, input/output or terminal connection for network connection via service interface (CDI-RJ45) Protective earth (PE) –...
Page 31
Proline 500 HART Electrical connection N ic N ic t e r t e r e r g ö f f e r g ö f f iz e iz e t e n t e n r ir r ir...
Electrical connection Proline 500 HART 22 mm 24 mm – A0029816 10. Connect the cable in accordance with the terminal assignment . Signal cable terminal assignment: The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
Page 33
• Grounding rings can be ordered separately as an accessory from Endress+Hauser . When ordering make sure that the grounding rings are compatible with the material used for the...
Page 34
Electrical connection Proline 500 HART Potential equalization via grounding electrodes on process connection A0028972 Hexagonal-headed bolts of process connection Integrated grounding electrodes O-ring seal Sensor 5.3.2 Promag P and Promag W For devices intended for use in hazardous locations, please observe the guidelines in the Ex documentation (XA).
Page 35
Proline 500 HART Electrical connection Ground cable Copper wire, at least 6 mm (0.0093 in DN 300 DN 350 ≥ ≤ A0029338 4 Potential equalization via ground terminal and pipe flanges Connect both sensor flanges to the pipe flange via a ground cable and ground them.
Electrical connection Proline 500 HART Pipe with a cathodic protection unit This connection method is only used if the following two conditions are met: • Metal pipe without liner or pipe with electrically conductive liner • Cathodic protection is integrated in the personal protection equipment...
Proline 500 HART Electrical connection To ensure that moisture does not enter the cable entry: Route the cable so that it loops down before the cable entry ("water trap"). A0029278 Insert dummy plugs into unused cable entries. Post-connection check Are cables or the device undamaged (visual inspection)? ...
Operation options Proline 500 HART Operation options Overview of operation options A0034513 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370 Mobile handheld terminal Control system (e.g.
Proline 500 HART Operation options Structure and function of the operating menu 6.2.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN 6 Schematic structure of the operating menu 6.2.2...
Operation options Proline 500 HART Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W +0.000 Xx...
Page 41
Proline 500 HART Operation options 6.3.1 Operational display Explanatory symbols for the measured value Status area • Depends on the device version, e.g.: The following symbols appear in the status area of the – : Volume flow operational display at the top right: –...
Page 42
Operation options Proline 500 HART Numeric editor Confirms selection. Moves the input position one position to the left. Exits the input without applying the changes. Inserts decimal separator at the input position. Inserts minus sign at the input position. Clears all entered characters.
Proline 500 HART System integration Keys and meaning Reduces the contrast (brighter setting). Plus/Enter key combination (press and hold down the keys simultaneously) Increases the contrast (darker setting). Minus/Plus/Enter key combination (press the keys simultaneously) For operational display:Enables or disables the keypad lock.
Commissioning Proline 500 HART • "Post-installation check" checklist → 16 • "Post-connection check" checklist → 37 Setting the operating language Factory setting: English or ordered local language X X X X X X X 20.50 Main menu 0104-1...
Proline 500 HART Diagnostic information Example: Available submenus, wizards Meaning System units Configure the units for all measured values I/O configuration User configurable I/O module Current input Configuration of the input/output type Status input Current output 1 to n Pulse/frequency/switch output 1 to n...
Page 46
Diagnostic information Proline 500 HART X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2 Diagnostics 3 Supply voltage (ID:203) S801 0d00h02m25s...