Step 15 Setting The Indoor Unit Addresses; Step 16 Additional Functions - Samsung AJ RBLDEG Series Installation Manual

Table of Contents

Advertisement

Installation Procedure
External Static Pressure
External Static
1.0
Pressure (mmAq)
AJ026RBLDEG 015201-1400FB 015201-14020C 015201-140360 015201-1403A2
AJ035RBLDEG 015201-16025D 015201-16026E 015201-1603C4 015203-160108
External Static
0.0
Pressure (mmAq)
AJ052RBMDEG 012221-194247 012221-194360 012221-1943A2 012223-194105
• Mark '
' is the basic model of this product.
Refer to the table above depending on the installation
environment.
Step 15 Setting the Indoor unit
addresses
1 Before installing the indoor unit,assign an address to the
indoor unit according to the air conditioning system plan.
2 The address of the indoor unit is assigned by adjusting
MAIN(SW02) switch.
3 The MAIN address is for communication between the
indoor unit and the outdoor unit. Therefore, you must set
it to operate the air conditioner properly.
4 It is required to set the RMC address if you install the wired
remote controller and/or the centralized controller.
5 If you install optional accessories such as the wired
remote controller, centralized controller, etc. see an
appropriate installation manual.
6 If an optional accessory is not installed, you do not have
to set the RMC address. However, adjust K1 and K2
switches of the SW05 DIP switch to "ON" position in this
case.
7 Set the MAIN address by adjusting the rotary
switch(SW02) from 0 to 9. Each indoor unit connected to
the same outdoor unit must have different address.
20
English
2.0
3.0
4.0
2.0
4.0
6.0
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10K11 K12

Step 16 Additional Functions

NO.
Function
K1
External room sensor
K2
Centralized controller
SW05
K3
Compensate RPM
K4
Drain Pump
• K1 OFF
Heating mode : Setting temperature compensation
value = 0°C
Thermo OFF
Fan OFF
NO.
Function
Indoor Temperature
K5
Compensation for Heating Mode
K6
Filter Time
SW06
K7
Hot Water Coil
K8
-
NO.
Function
K9
-
K10
-
SW07
K11
External control
K12
External Control Output
SW05
ON
OFF
Not use
Use
Not use
Use
Standard
Up
Not use
Use
SW06
ON
OFF
+2°C
+5°C
1,000
2,000
hours
hours
Not Use
Use
-
-
SW07
ON
OFF
-
-
-
-
Not Use
Use
Thermal ON Operation ON