Connecting High Ac/Dc Power - Siemens SIMATIC NET RUGGEDCOM RS900W Installation Manual

Rugged
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS900W:
Table of Contents

Advertisement

2.6.1

Connecting High AC/DC Power

To connect a high AC/DC power supply to the device, do the following:
NOTICE
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to terminals for DC power. Damage to the power
supply may occur.
NOTICE
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the braided
ground cable connected to the surge ground terminal and chassis ground. This cable
connects transient suppression circuitry to chassis ground and must be removed in
order to avoid damage to transient suppression circuitry during testing.
Note
Torque all terminal connections to 0.6 N·m (5 lbf-in).
1.
RUGGEDCOM RS900W
Installation Manual, 02/2020, C79000-G8976-1028-10
Secure the power terminal block to the device.
Installing the Device
2.6.1 Connecting High AC/DC Power
13

Advertisement

Table of Contents
loading

Table of Contents