Planning How To Position The Chassis In The Rack - Cisco Nexus 93216TC-FX2 Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Installing the Chassis
The shipment should include the following:
• Switch chassis, which includes the following installed components:
• Two power supplies (any combination of the following with the airflow direction being the same as for the fan
modules):
• fan modules (all fan and power supply modules must have the same airflow direction)
• Switch accessory kit
Step 2
Check the contents of the box for damage.
Step 3
If you notice any discrepancies or damage, send the following information to your customer service representative by
email:
• Invoice number of the shipper (see the packing slip)
• Model and serial number of the missing or damaged unit
• Description of the problem and how it affects the installation

Planning How to Position the Chassis in the Rack

The switch is designed so that you can have coolant air flow through the switch in one of the two following
directions:
• Enter the port side and exhaust out the power supply side (port-side intake airflow)
• Enter the power supply side and exhaust out the port side (port-side exhaust airflow)
For port-side intake airflow, the switch must have port-side intake fan and AC power supply modules with
one or more of the following colorings:
• Burgundy coloring on fan modules and AC power supplies
For port-side exhaust airflow, the switch must have port-side exhaust fan and AC power supply modules with
one or more of the following colorings:
• Blue coloring on fan modules and AC power supplies
You can plan the positioning of the switch so that its ports are located close to ports on connected devices or
so that the fan and power supply modules are conveniently located in a maintenance aisle, and then order the
modules that move coolant air in the appropriate direction from the cold aisle to the hot aisle.
Note
All fan and power supply modules in the same switch must operate with the same direction of airflow and
the air intake portion of the switch must be located in a cold aisle.
Cisco Nexus 93216TC-FX2 ACI-Mode Switch Hardware Installation Guide

Planning How to Position the Chassis in the Rack