Planning How To Position The Chassis In The Rack - Cisco Nexus 9396PX Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Installing the Chassis
• Two power supplies (any combination of the following with the airflow direction being the same as for the fan
modules):
• 650-W AC power supply
• 930-W DC power supply
• Three fan modules (all fan and power supply modules must have the same airflow direction)
• Port-side exhaust airflow with blue coloring (N9K-C9300-FAN2-B)
• Port-side intake airflow with burgundy coloring (N9K-C9300-FAN2)
• Switch accessory kit
• Rack mount kit
Step 2
Check the contents of the box for damage.
Step 3
If you notice any discrepancies or damage, send the following information to your customer service representative by
email:
• Invoice number of the shipper (see the packing slip)
• Model and serial number of the missing or damaged unit
• Description of the problem and how it affects the installation

Planning How to Position the Chassis in the Rack

The switch is designed so that you can have coolant air flow through the switch in one of the two following
directions:
• Enter the port side and exhaust out the power supply side (port-side intake airflow)
• Enter the power supply side and exhaust out the port side (port-side exhaust airflow)
For port-side intake airflow, the switch must have port-side intake fan and AC power supply modules with
one or more of the following colorings:
• Burgundy coloring on fan modules and AC power supplies
• Green coloring on DC power supplies
• Port-side exhaust airflow with blue coloring (N9K-PAC-650W-B)
• Port-side intake airflow with burgundy coloring (N9K-PAC-650W)
• Port-side exhaust airflow with gray coloring (UCS-PSU-6332-DC)
• Port-side intake airflow with green coloring (UCSC-PDU-930WDC)

Planning How to Position the Chassis in the Rack

Cisco Nexus 9396PX ACI-Mode Switch Hardware Installation Guide
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

N9k-c9396px

Table of Contents