Grounding the Device

The RUGGEDCOM RS400 chassis ground terminal uses a #6-32 screw. It is recom-
mended to terminate the ground connection with a #6 ring lug and torque it to 1.7
N·m (15 lbf·in).
1
2
3
Figure 2.6
2.6

Connecting Power

The RUGGEDCOM RS400 supports a single integrated high AC/DC or low DC power
supply
RUGGEDCOM RS400
Installation Manual, 02/2020, C79000-G8976-1016-10
1
2
3
Normally Closed
Common
Normally Open
Failsafe Alarm Relay Wiring
1
Stainless Steel Stud
#6-32 Screw
#6 Ring Lug
Chassis Ground Connection
2
3
Installing the Device
2.5 Grounding the Device
13