Daikin RXSQ24TAVJUA Installation Manual page 22

Residential vrv system air conditioner
Table of Contents

Advertisement

Heat pump lockout temperature
Heat pump would be locked out when the outdoor ambient temperature is smaller than the heat pump lockout temperature.
This setting is only effective when heat pump lockout mode has been set.
When connecting with multiple G/Fs, should make the following settings.
And should make the field setting of indoor. About indoor setting, see indoor installation manual.
Setting item display
No.
MODE
TEST
Setting item
H1P
H2P
Heat pump
k
k
57
lockout
temperature
Heat pump lockout release differential
Heat pump would be resumed when the outdoor ambient temperature is recovered by differential above the heat pump lockout temperature.
No.
MODE
TEST
Setting item
H1P
H2P
Heat pump
lockout
k
k
47
release
differential
Automatic lockout
When heat pump lockout mode has been set, the auto backup function will automatically be set. This will allow the auxiliary or secondary heat source
to be automatically energized in the event of a system failure related to outdoor units.
18
C/H selection
Low
noise
IND
Master
Slave
H6P
H3P
H4P
H5P
k
k
h
h
Setting item display
C/H selection
Low
noise
IND
Master
Slave
H6P
H3P
H4P
H5P
h
k
k
k
Setting condition display
Demand
H7P
k h h h h h h
–26.1°C (–15°F)
k h h h h h k
–23.3°C (–10°F)
k h h h h k h
–20.5°C (–5°F)
k h h h h k k
–17.7°C (0°F)
k h h h k h h
–15°C (5°F)
k h h h k h k
–12.2°C (10°F)
k h h h k k h
–9.4°C (15°F)
k
k h h h k k k
–6.6°C (20°F)
k h h k h h h
–3.8°C (25°F)
k h h k h h k
–1.1°C (30°F)
k h h k h k h
1.6°C (35°F)
k h h k h k k
4.4°C (40°F)
k h h k k h h
7.2°C (45°F)
k h h k k h k
10°C (50°F)
Forced heat
k h h k k k h
pump lockout
Setting condition display
Demand
H7P
k h h h h h h
2.8°C (5°F)
k
k h h h h h k
5.6°C (10°F)
k h h h h k h
8.3°C (15°F)
Factory setting
Factory setting