Page 1
INSTALLATION MANUAL Residential VRV System Air Conditioner Installation manual MODEL English Residential VRV System air conditioner RXSQ24TAVJUA RXSQ36TAVJUA Manuel d’installation Français RXSQ48TAVJUA Climatiseur à système VRV résidentiel Manual de instalación Español Acondicionador residencial de aire sistema VRV...
Page 2
figure 1 figure 2 inch(mm) inch(mm) figure 3 figure 4 40(1000) 40(1000) 40(1000) 40(1000) or more or more or more or more 40(1000) 40(1000) or more or more inch(mm) inch(mm) inch(mm) inch(mm) figure 5 figure 6 L > H L > H L >...
Page 3
40(1000) 40(1000) or more or more L > H inch(mm) figure 8 RXSQ48 type inch(mm) inch(mm) figure 9 figure 10 figure 14 13/16 (20) inch(mm) figure 11 figure 12 figure 15 Lock nut Cover Lock nut Cover Conduit 6-5/16 (160) 24-3/8 (620) 6-5/16 (160) Conduit...
Page 4
(X2M) (X1M) (X1M) Keep proper distance (X2M) RXSQ24 type RXSQ48 type RXSQ36 type figure 17 TO IN/D UNIT TO OUT/D UNIT F2 F1 F2 F1 F2 F1 F2 F1 F2 figure 18 figure 21 figure 19 figure 20 figure 22 figure 23 figure 24 figure 25...
Installation manual Residential VRV System air conditioner NOTE.....Indicates situations that may result in equipment or CONTENTS property-damage accidents only. 1. SAFETY CONSIDERATIONS ..........1 2. INTRODUCTION..............2 DANGER 2-1. Combination ..............3 • Refrigerant gas is heavier than air and replaces oxygen. A mas- 2-2.
2-1 Combination 2-3 Standard supplied accessories The indoor units can be installed in the following range. Make sure that the accessories shown below are all present. • Be sure to connect a dedicated indoor unit. See the catalog for (The accessories can be found behind the front panel.) indoor unit models which can be connected.
Page 8
• A locations where there is enough space to install the unit. (Refer to figure 4) 1. Indoor unit • Places where the indoor and outdoor unit’s piping and wiring 2. Fuse/Breaker lengths come within the allowable ranges. 3. Remote controller •...
Series installation (up to two units) (Refer to figure 8-[4]) (7)-5 IN CASE OF MULTIPLE-ROW INSTALLATION (FOR ROOF Relation of dimensions of H, A, and L are shown in the table below. TOP USE, ETC.) inch(mm) In case of installing one unit per row (Refer to figure 10-[1]) In case of installing multiple units (2 units or more) in lateral connec- tion per row (Refer to figure 10-[2]) 0 <...
FIELD WIRING 4. 16V 5. 208/230V 6. Indoor unit CAUTION 7. Remote controller To the electrician 8. Ground wire • Do not operate until refrigerant piping work is completed. 9. Indoor unit (CXTQ**) (Failure to adhere by this caution may lead to irrepairable 10.
<Precautions when laying power wiring> 4. Ground wire (Yellow/Green) • Wiring of different thicknesses cannot be connected to the power ter- 5. Terminal block (X1M) minal block. 6. Transmission wiring (Slack in the power wiring may cause abnormal heat.) 7. (To X2M [TO IN/ D UNIT] (F1, F2)) •...
7-1 Selecting piping material • Be sure to perform a nitrogen blow when brazing. (Brazing without performing nitrogen replacement or releasing nitro- gen into the piping will create large quantities of oxidized film on the CAUTION inside of the pipes, adversely affecting valves and compressors in the Piping and other pressure containing parts shall comply with the refrigerating system and preventing normal operation.) applicable legislation and shall be suitable for refrigerant.
• Insulation is required to all gas pipe. • If a torque wrench is not available, there is a place where the tight- • When the gas pipe diameter is larger than the specified pipe diam- ening torque will suddenly increase if a normal wrench is used to eter, add the amount of refrigerant according to “7-7 Additional tighten the flare nut.
7-8 Air tight test and vacuum drying • Since the side boards may be deformed if only a torque wrench is used when loosening or tightening flare nuts, always lock the stop After doing the piping, perform the following inspections. valve with a wrench and then use a torque wrench.
ADDITIONAL REFRIGERANT CHARGE 8-2 Checking the refrigerant tank • Check whether the tank has a siphon pipe before charging and place WARNING the tank so that the refrigerant is charged in liquid form. (See the fig- ure below.) • When leaving the unit with the power on, be sure to switch with another person doing the installation or close Tank with siphon pipe Other tanks...
10-2 Temperature control operation checklist • During the operation, monitor the outdoor unit operation status and check for any incorrect wiring. [Set the master unit (the indoor unit with rights of selection cooling or heating)] 1. Close the outdoor unit’s front panel. Be sure to turn the power on at least Caution <With a wired remote controller>...
10-3 Final charge adjustment [Remote controller displays malfunction code] (Check on a remote controller connected to the indoor unit.) It is not necessary to do this final adjustment normally, but perform the Malfunc- following operation only when the most adequate refrigerant charge for Installation error Remedial action tion code...
Using this idea, the system automatically starts decreasing its refrig- • Mild erant temperature, automatically reducing the delivered capacity Overshoot (during heating operation) or undershoot (during cooling and increasing the system’s efficiency. operation) is allowed compared to the requested refrigerant tem- •...
11-4 Setting of Heat Pump Lockout and Emergency Heat Mode Heat pump is locked out when the setting below and/or external input to ABC terminal has been made. Setting item display Setting condition display C/H selection MODE TEST Demand Setting item noise Master Slave...
Page 22
Heat pump lockout temperature Heat pump would be locked out when the outdoor ambient temperature is smaller than the heat pump lockout temperature. This setting is only effective when heat pump lockout mode has been set. When connecting with multiple G/Fs, should make the following settings. And should make the field setting of indoor.
11-5 Setting of larger pipe connection and no insulation on liquid line When using existing piping, make the following settings. Setting item display Setting condition display C/H selection MODE TEST Demand Setting noise Master Slave Factory setting item Standard pipe connection k h h h h h h Gas side: Standard diameter...
Page 24
Example: Automatic mode during cooling Example: Automatic mode during heating 100% 100% 120°F (49°C) 115°F (46°C) 43°F (6°C) 37°F (3°C) 95°F (35°C) 36°F (2°C) A Actual load curve A Virtual load curve (default automatic mode peak capacity) B Virtual load curve (initial capacity automatic mode) B Load curve C Virtual target value (initial evaporation temperature C Virtual target value (initial condensation tempera-...