Toshiba RAS-3M26U2AVG-E Service Manual page 98

Hide thumbs Also See for RAS-3M26U2AVG-E:
Table of Contents

Advertisement

No.
Part name
∗ Attachment
TG sensor
17
TGc: Green
TGb: Red
TGa: Yellow
NOTE)
When mounting the sensors, check paint color
of the sensor lead tube part and the pipe color.
Mount the sensors to the position of same color.
Detail G
Sensor wiring
• Using bundling band, bind PMV coil
18
process
• For Td sensor, bind the case thermo and
Bundling band
PMV coil (Green to Yellow)
TGa to TGc sensors
Bundling band
Td sensor
Case thermo
Reactor lead
NOTE)
Using the bundling band being on the market,
be sure to bind the position which was bound.
Procedure
Mount these sensors on the directly arranged
part of the header connecting pipe at gas side
so that the cabinet turns toward the front side
and the sensors turn toward upper cabinet.
(Green to Yellow) with Tga to Tgc.
reactor lead by bundling band.
Pass TG sensor through the
upper side of connecting pipe of
PMV unit (Green) and then bind
it with lead wire of PMV coil.
TGc: Green
TGb: Red
TGa: Yellow
NOTE)
At working time (finish time), be
sure not to damage the cover of
the sensor lead wire with edge of
sheet metal, etc.
If the cover of the sensor lead
wire is damaged, it is dangerous
because an electric shock or fire
may be caused.
NOTE)
After replacing of parts, check
the sensors are mounted at the
specified positions.
If there are incorrect mounted
positions, control of the product
does not operate correctly and a
trouble may be caused.