Information Mapping Table - Siemens SICAM P37 Manual

3-phase harmonic power meter
Table of Contents

Advertisement

Communication

6.2.4 Information mapping table

6.2.4
Information mapping table
Common Parameters
Parameter
Modbus address
Baud rate of
communication
High 16 bits of
voltage ratio part
Low 16 bits of
voltage ratio part
High 16 bits of
current ratio part
Low 16 bits of
current ratio part
Clearing extreme
value
Parity
Relay Alarm Parameters
Parameter
Relay output 1
Relay output 2
Binary inputs
44
Address
Data Type
0000 H
unsigned int
0001 H
unsigned int
0002 H
unsigned long
0003 H
0004 H
unsigned long
0005 H
0006 H
unsigned int
0020 H
unsigned int
Address
Data Type
0100 H
unsigned int
0101 H
unsigned int
0102 H
unsigned int
Length
R/W
Data Range
2 bytes
R/W
0...247
2 bytes
R/W
4 bytes
R/W
0...99999999
4 bytes
R/W
0...99999999
2 bytes
W
Arbitrary value
2 bytes
R/W
Data
Length
R/W
Range
2 bytes
R/W
0...1
2 bytes
R/W
0...1
2 bytes
R
SICAM P37, 3-phase Harmonic Power Meter, User Manual
E50417-H8940-C563-4, Release Date 06.2018
Remark
0: 2400 bps
1: 4800 bps
2: 9600 bps
0...6
3: 19200 bps
4: 38400 bps
5: 600 bps
6: 1200 bps
PT ratio=set val-
ue/10,000, 10,000
as default when
PT=0
CT ratio=set val-
ue/10,000, 10,000
as default when
CT=0
0: 8E1
1: 8o1
0...3
2: 8n1
3: 8n2
Remark
Write operation is valid
when "alarm manner
control byte" is 0 or 2
Write operation is valid
when "alarm manner
control byte" is 0 or 1
High byte: binary input
status (note)
Low byte: binary output
status