Info Menu; User Settings Menu - Daikin D2C24ND035A5AA Operation Manual

Wall-mounted condensing boiler
Hide thumbs Also See for D2C24ND035A5AA:
Table of Contents

Advertisement

Available languages

Available languages

3 Operation
3.5.2

Info menu

Info menu: Parameters
The info menu ( ) covers all possible information that is made
available to the end user and to the installer. This parameters are
read only and cannot be changed.
#
Description (short)
A00
Actual flow temperature
A01
Actual return temperature
A02
Actual domestic hot water temperature
A03
Actual flue temperature
(a)
A04
Actual outdoor temperature
(a)
A05
Actual solar temperature
A06
Actual water pressure
A07
Actual domestic hot water flow rate
(b)
A08
Current set point of burner capacity
(b)
A09
Actual capacity of boiler in relation to
nominal capacity
(c)
A10
Actual phase of the burner
A11
Status of On-Off room thermostat,
indicate heat demand (HC1)
A12
Actual error code of boiler
A13
Actual fan speed (rpm/100)
A14
Current setpoint of boiler pump
(d)
F11
Fuel energy consumption / Central
Heating / Last month
(d)
F12
Fuel energy consumption / Central
Heating / Current month
(d)
F13
Fuel energy consumption / Central
Heating / Current Year
(d)
F21
Electric energy consumption / Central
Heating / Last month
(d)
F22
Electric energy consumption / Central
Heating / Current month
(d)
F23
Electric energy consumption / Central
Heating / Current Year
(d)
F31
Fuel energy consumption / Domestic hot
water / Last month
(d)
F32
Fuel energy consumption / Domestic hot
water / Current month
(d)
F33
Fuel energy consumption / Domestic hot
water / Current Year
(d)
F41
Electric energy consumption / Domestic
hot water / Last month
Operation manual
8
#
(d)
F42
Electric energy consumption / Domestic
hot water / Current month
(d)
F43
Electric energy consumption / Domestic
hot water / Current Year
(a)
Not applicable if the sensor is not connected.
(b)
Maximum value for central heating = 91%
Maximum value for domestic hot water = 100%
(c)
A10=0: Standby mode, burner is not active
A10=1: Start-up, preparation to ignition
A10=2: Ignition and flame stabilisation phase
A10=3: Release control (burner is on, operation phase)
A10=4: Post-purge phase
(d)
Applicable if energy metering is enabled. Consumed
energy values are shown with 6 digits. The display
sequence is: parameter ID – first 3 digits – last 3 digits.
E.g. if 3456 kWh central heating fuel energy consumed in
current month, following screens are displayed in a
sequence of; F12 – 003 - 456
To use the info menu
1 Press the "Enter" button when the
menu level 1 screen.
2 Select A or F parameters with the left dial.
3 Select the index number with the right dial. Press the "Back"
button to return to menu level 1 screen.
Unit
°C
°C
°C
°C
°C
°C
bar
l/min
%
%
a
Index
3.5.3

User settings menu

rpm
%
User settings menu: Parameters (short)
kWh
The user settings menu ( ) comprises parameters that can be
changed and adjusted by users. You can read out and adjust the
kWh
parameters according to your preferences.
kWh
NOTICE
If you are not sure about the function of the parameter, do
kWh
not change it. Contact your service agent.
#
kWh
U00
Summer-winter switch over
temperature
kWh
U01
Heating slope
kWh
U02
Central heating ECO mode
U03
Domestic hot water comfort
kWh
mode
U04
Domestic hot water set value
kWh
U05
Set value for the room
thermostat at day mode
kWh
Description (short)
icon is displayed on the
a
Description
Unit Default Range
°C
°C
°C
D2C20ND028A5AA + D2C24ND035A5AA
Wall-mounted condensing boiler
3P469438-10H – 2018.05
Unit
kWh
kWh
a
20
10~30
0
0~40
0
0~1
0
0~1
50
35~60