Cisco Nexus 93240YC-FX2 Hardware Installation Manual page 15

Nx-os mode switch
Hide thumbs Also See for Nexus 93240YC-FX2:
Table of Contents

Advertisement

Overview
Replaceable Modules
Fans
AC power supplies
HVAC/HVDC power supplies
DC power supplies
The fan and power supply modules are field replaceable. You can replace one fan module or one power supply
module during operations, so long as the other installed modules are operating. If you have only one power
supply that is installed, you can install the replacement power supply in the open slot before removing the
original power supply.
Note
Fan and power supply modules must have the same direction of airflow. Otherwise, the switch can overheat
and shut down. If you are installing a dual-direction power supply, that module automatically uses the same
airflow direction as the other modules in the switch.
Caution
If the switch has port-side intake airflow (burgundy coloring for fan modules), you must locate the ports in
the cold aisle. If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the
ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down.
The switch supports the Fabric Extenders (FEXs) listed at
datacenter/nexus9000/hw/interoperability/fexmatrix/fextables.html.
Port-Side Intake Airflow Coloring
Burgundy
Burgundy
Burgundy
https://www.cisco.com/c/dam/en/us/td/docs/switches/
Cisco Nexus 93240YC-FX2 NX-OS Mode Switch Hardware Installation Guide
Overview
Port-Side Exhaust Airflow Coloring
Blue
Blue
White
Blue
5