(Etiquette signalétique) HANDBUCH INSTRUÇÕES DE INSTALAÇÃO PHT 13 / 16 Pompe à chaleur haute température avec équipement hydraulique (chauffage seulement) - Fluide réfrigérant R 407 C High temperature heat pump with hydraulic equipment (heating only) - R 407 C refrigerant Refrigeratore d’acqua in versione pompa di calore alta temperatura con sezione idronica...
- use the anti-vibration mountings supplied, making sure that they are not A (m) compressed too much when the fastening screws are tightened, PHT 13/16 0.25 - due to disturbance which may be caused by the noise, the blown air must...
Page 5
• The sections are given as an indication only. They have to be verified and adapted, if necessary, according to the installation conditions and the standards in force. • Make the electrical connections to the terminal board as per the electrical diagrams. CURRENTS AND CROSS-SECTIONS PHT 13 PHT 16 400/3N/50 400/3N/50 Nominal current Max.
4.3.4 - REMOTE CONTROL • See paragraph "accessories". 4.3.5 - MISCELLANEOUS • Alarm transfer: Potential-free changeover contact (2A - 250 VAC max.) available on the unit's terminal strip (terminals 5 (common), 6 and 7 of the printed circuit) for remote signaling. See schematic. - In case of alarm: - contact open between terminals 5 and 6, - contact closed between terminals 5 and 7.
Page 7
5.3.2 - CTN TYPE TEMPERATURE PROBE Temperature (°C) Ohmic value (Ohm) • 10 kΩ at 25° C. 67 740 42 450 27 280 17 960 12 090 10 000 8 313 5 820 4 161 3 021 2 229 5.4 - OPERATING MODES •...
Page 8
5.6 - PARAMETERS - DISPLAYING AND ADJUSTING 5.6.1 - GENERAL • Parameter access is structured within a multi-level menu, see the diagram below. Simultaneously pressing the "ON/OFF" (1) and "Mode" (2) buttons for a brief moment (less than 2 seconds) gives access to the next level. Simultaneously pressing for a long moment (longer than 2 seconds) turns you to the previous level.
Page 9
5.6.3 - SET POINT ADJUSTMENT • Simultaneously press buttons (1) and (2) for at least 2 seconds, "SET" is displayed. • Press the 2 buttons again, "HEA" is displayed. • Simultaneously press the 2 buttons again for 2 seconds. The setpoint value appears. If needed, modify the value with the buttons.
Page 10
SUMMARY TABLE OF ALARMS Compressor Circulating pump Alarm Code Inhibition delay Fan stop Remarks shut-down stop Fault on probe 1 Fault on probe 2 Fault on probe 3 Forced circulating Fault on probe 4 pump operation H.P. B.P. (low pressure) 30'' at start-up From probe Anti-freeze (water...
6 - ACCESSORIES 6.1 - WATER CONNECTION HOSES • Length 1 m, insulated, female: - Ø 1” code 70600055 for PHT 13 and 16. 6.2 - REMOTE CONTROL • Code 70250055. • The functions and display are exactly the same as those on controller.
- Resistivity: 1 to 10 kΩ - Granulometry: < 0.4 mm - Fibre: no fibres Any disorder which may occur on our machines due to the poor quality of the fluid in the installation will not be covered by the TECHNIBEL warranty.
7.3 - STARTING-UP THE UNIT • Power up the unit. • Turn the water on. • Start the appliance (see paragraph 5). CAUTION: On three-phase units, make sure that the phase rotation order is correct. If the rotation order is not respected, If the rotation order is not respected, the phase-sequence controller restricts the unit from operating (indicator OK off).
Note: The water flow is selected according to the maximum water outlet temperature at which the pump will operate (depending on the application). CIRCULATOR SXM 25 - 90 CIRCULATOR SXM 32 - 80 PHT 13 PHT 16 Speed 2 Speed 1...
11 - PRESSURE TABLES Low pressure High pressure PHT 13 Water outlet temperature Water outlet temperature 45° C 55° C 60° C 45° C 55° C 60° C 1.24 18.43 1.34 18.52 1.45 18.61 1.55 18.70 1.66 18.79 1.76 18.87 1.87...
Page 16
Low pressure High pressure PHT 16 Water outlet temperature Water outlet temperature 45° C 55° C 60° C 45° C 55° C 60° C 1.51 19.35 1.56 19.37 1.61 19.39 1.66 19.42 1.71 19.45 1.76 19.48 1.81 19.50 1.95 19.53 2.05 19.56 2.14...
High pressure switch Black temperature probe M11 Fan Low pressure switch SD4 Outside air probe Compressor EV1 Electrovalve White ELECTRICAL DIAGRAM - PHT 13/16 - 400/3N/50 10 05 816 - 00 Controller Filter Interface panel Alarm Fan 1 Fan 2 Compressor...
Page 20
Par souci d'amélioration constante, nos produits peuvent être modifiés sans préavis. Due to our policy of continuous development, our products are liable to modification without notice. Per garantire un costante miglioramento dei nostri prodotti, ci riserviamo di modificarli senza preaviso. En el interés de mejoras constantes, nuestros productos pueden modificarse sin aviso prévio.