Waterside Pressure Drop Table; Water Coil Volume - Bosch SV007 Installation, Operation And Maintenance Manual

Model sv - i series geothermal heat pump
Table of Contents

Advertisement

44 | Waterside Pressure Drop Table

WATERSIDE PRESSURE DROP TABLE
Water
Water Side
Flow
Model
Pressure Drop
Rate
(GPM)
1.5
SV007
2
2.5
2
SV009
2.5
3
2.5
SV012
3
3.5
3
SV015
4
5
4
SV018
5
6
4
SV024
6
8
5
SV030
7.5
9
6
SV036
9
12
7
SV041
10
13
7
SV042
10
13
8
SV048
12
15
10
SV060
15
18
11
SV070
16
18
All values based upon pure water at 70° F.
8 733 914 818 (2014?08)
Water Side
Pressure Drop
with Internal
(PSI)
Valve (PSI)
0.7
1.0
1.1
1.8
1.7
2.7
1.7
2.3
2.5
3.5
3.5
5.0
2.6
3.6
3.6
5.0
4.8
6.7
3.9
5.3
6.5
9.1
9.8
13.8
2.7
5.2
4.0
8.0
5.6
11.3
2.8
3.4
5.8
7.2
9.7
12.3
3.0
4.0
6.2
8.5
8.6
11.9
2.6
4.0
5.4
8.6
9.1
14.8
3.6
5.6
6.9
10.9
11.1
17.9
3.6
5.6
6.9
10.9
11.1
17.8
1.4
2.5
2.8
5.4
4.2
8.2
2.3
4.1
4.8
8.8
6.7
12.4
2.9
5.0
5.7
10.2
7.0
12.7
Subject to change without prior notice

WATER COIL VOLUME

SV Series
Coaxial Coil Volume (gal)
007
009
012
015
018
024
030
036
041
042
048
060
070
SV Heat PumpSeries
0.04
0.06
0.08
0.09
0.14
0.14
0.24
0.27
0.27
0.27
0.49
0.62
0.62
SV Heat Pump Series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents