Freeze Prevention (Cooling And Dry) - Sanyo SAP-K77GHAX Technical & Service Manual

Table of Contents

Advertisement

8-4. Freeze Prevention (Cooling and Dry)

This function prevents freezing of the indoor heat exchange coil.
When the temperature of the indoor heat exchange coil falls below 2 C for 2 minutes, the control circuit stops
the outdoor fan and compressor (The compressor stops 3 seconds after the outdoor fan stopped). During this
period, Indoor fan operates in LL. The outdoor fan does not start again until the temperature rises above 6 C.
(The compressor starts 2 seconds after the outdoor fan started.)
Indoor heat
exch. coil
temp.
Outdoor fan
Compressor
Indoor fan
6 C
2 C
Set Speed
At least
approx. 2 min.
3 sec.
ON
ON
48
OFF
ON
2 sec.
OFF
ON
Set Speed
LL