Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
CAUTION
r o
u
n
t i
Wide tube
O.D.
12.7 mm
(1/2 ")
Narrow tube
O.D.
6.35 mm
(1/4")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Outdoor Unit SAP-C127GHAX
O
u
d t
Wide tube
service
valve
Narrow
tube
Capillary tube
service
(for heating)
valve
Check
valve
Thickness:
Min. 8 mm
20
o
r o
u
n
t i
Accumulator
4-way
valve
Capillary tube
(
)
both for heating
and cooling
Insulation
Wide tube
Cooling cycle
Heating cycle
Thickness:
Min. 8 mm
Narrow tube