Installation, Maintenance & Troubleshooting guide | Version 05
5. LMR-A: Auto mode
b. WLCA- Suction mode
16A
: Motor suddenly stops after running for some time.
16B
: Check the mode of LMR-A, if it is Auto mode.
16C
: Check the mode of WLCA, if it is Suction mode.
16D
: Amber LED will start blinking
16E to 16G : Follow steps from 15H to 15J of LMR-A Manual mode & WLCA delivery mode
(Refer Table no.27, Corrective action 1)
16H
: No need to press ON push button
16I
: Starter switches ON automatically.
16J
: Green LED turns ON indicating that the starter is ON.
16K
: Motor starts running again.
16L
: Water gets drawn out of the suction tank till the water level goes below P2 sensor.
6. LMR-A: Auto mode
c. WLCA- Dual tank mode
16A
: Motor suddenly stops after running for some time.
16B
: Check the mode of LMR-A, if it is Auto mode.
16C
: Check the mode of WLCA, if it is Dual tank mode.
16D
: Amber LED will start blinking
16E to 16G : Follow steps from 15H to 15J of LMR-A Manual mode & WLCA Delivery mode
(Refer Table no.27, Corrective action 1)
16H
: No need to press ON push button
16I
: Starter switches ON automatically.
16J
: Green LED turns ON indicating that the starter is ON.
16K
: Motor starts running again.
16L
: Delivery tank gets filled from the suction tank till the water in the delivery tank touches the level of
P3 sensor or till the water level in the suction tank reaches below P2 sensor.
λλ LMR-A: Bypass mode
a. WLCA- In any 3x mode (Delivery, Suction, Dual Tank)
As in Bypass mode there is no protection from the incoming supply faults, however there may be some conditions,
example mentioned below where Starter may not ON –
1. Phase loss
2. Incoming supply voltage less than the minimum required operational voltage of the Starter.
3. Incoming supply voltage is very high etc.......
Also check the WLC-A faults which may arise due to the sensor misplacement in the tank.Refer 6Note
In the above conditions check the Starters as explained in Auto & Manual Mode.
25