Installation - Siemens Raja+ 3TE7431-2BC24-1A Series Installation, Maintenance & Troubleshooting Manual

Agriculture starters & controllers

Advertisement

Installation, Maintenance & Troubleshooting guide | Version 05

5.4: Installation

• Open the door by rotating the door lock anticlockwise.
• Mount the starter on a vertical wall/ plate free from vibrations with proper nuts and bolts.
Refer operating instruction for mounting dimensions.
• Remove the rubber grommets for the incoming and outgoing cable connections. (Refer Fig. 13)
• Connect incoming and outgoing cables as follows (Refer Fig. 13):
- Use proper cable glands to ensure dust proofing. For conduit entry use packed washers.
- Select correct size of cables from Table 25
- Connect line and motor leads exactly as per wiring diagram pasted inside the cover of the starter.
- Terminate the incoming supply cables on terminal block TB1 & outgoing cables to motor on terminal block TB2,TB3
(Tightening torque -Refer table 25B)
NOTE: LMRA is set in Manual mode (Factory setting)
WLCA is set in Delivery mode (Factory setting)
- Connect the earthing conductor to terminals marked (earth) on the starter body with torque 1.2 to 1.6Nm.
The Starter is now ready for commissioning.
• Initially set the overload relay to 0.58 times the rated motor current.
• Set the timer dial to the nearest value of starting time available on motor nameplate
• If it is not available, then set the dial to approximately 6-8secs.
Commissioning :
For exact setting of timer and overload relay, follow the instruction given
below:
Before switching ON recheck all external connections.
• Star-Delta Timer setting for FASD:
- First Switch ON the Rocker switch.
- Start the motor by pressing the 'ON' button shown in Fig. 12
- Measure the time taken by the motor to nearly reach rated speed or
steady state current condition (indicated when the motor reaches a
steady hum).
- Stop the motor. Set the timer to this measured value by rotating the
dial shown in Fig. 13A.
• Overload relay setting:
- For closer protection set the overload relay to actual phase current as measured by an ammeter. In the absence of an
ammeter, use the procedure given below:
- Start the motor and let it run for 30 mins. Then gradually reduce the relay settings till it trips. Set the relay at a slightly higher
value than this setting. Overload relay characteristics shown in Fig. 6 can be used to estimate the average tripping time at
different multiples of set current.
- Allow a reset time of approx. 4 min. before pressing the blue knob on the relay to reset it.
- Restart the motor after some time. If the relay does not trip then consider it to be properly set. If the relay trips, set at a little
higher value than before and recheck.
• Close the front door.
Fig. 13A: Timer Adjustment
10