Table 13 — Fan Performance — 581A300 High Heat Vertical Discharge Units*
AIRFLOW
0.2
(Cfm)
Rpm
Watts
6,500
775
2,600
7,000
826
3,115
7,500
878
3,690
8,000
929
4,326
8,500
981
5,029
9,000
1033
5,799
9,500
1085
6,640
10,000
1137
7,553
10,500
1190
8,542
11,000
1242
9,609
11,500
1294
10,756
12,000
1347
11,985
12,500
AIRFLOW
1.2
(Cfm)
Rpm
Watts
6,500
1004
4,016
7,000
1041
4,559
7,500
1081
5,179
8,000
1124
5,875
8,500
1168
6,647
9,000
1214
7,495
9,500
1260
8,421
10,000
1308
9,425
10,500
1356
10,510
11,000
11,500
12,000
12,500
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive ranges:
Low Range: 941-1176
High Range: 1014-1297
All other rpms require field-supplied drive.
1. Static pressure losses (i.e., EconoMi$er IV) from Table 26 must be
added to external static pressure before entering Fan Performance
table.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance is based on wet coils, clean filters, and casing
losses. See Table 26 on page 30.
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
Bhp
Rpm
Watts
Bhp
2.99
825
2,872
3.30
3.58
875
3,408
3.92
4.24
925
4,006
4.61
4.98
975
4,667
5.37
5.78
1026
5,395
6.20
6.67
1076
6,191
7.12
7.64
1128
7,058
8.12
8.69
1179
8,000
9.20
9.82
1230
9,016
10.37
11.05
1282
10,111
11.63
12.37
1333
11,287
12.98
13.78
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
Bhp
Rpm
Watts
Bhp
4.62
1050
4,374
5.03
5.24
1083
4,902
5.64
5.96
1120
5,512
6.34
6.76
1160
6,203
7.13
7.64
1202
6,974
8.02
8.62
1245
7,825
9.00
9.69
1290
8,756
10.07
10.84
1337
9,768
11.23
12.09
1384
10,862
12.49
GENERAL NOTES FOR TABLES 5-22
0.6
Rpm
Watts
Bhp
Rpm
871
3,130
3.60
915
918
3,679
4.23
959
966
4,292
4.94
1005
1015
4,970
5.72
1052
1064
5,717
6.58
1100
1114
6,533
7.51
1148
1164
7,421
8.54
1198
1214
8,385
9.64
1247
1265
9,424
10.84
1297
1316
10,542
12.12
1347
1367
11,741
13.50
1.6
Rpm
Watts
Bhp
Rpm
1098
4,769
5.48
1145
1126
5,277
6.07
1170
1159
5,872
6.75
1199
1196
6,553
7.54
1233
1235
7,318
8.42
1269
1277
8,168
9.39
1309
1320
9,100
10.47
1351
1365
10,116
11.63
1394
Refer to this page for general Fan Performance Data notes.
NOTE: Maximum continuous bhp is:
Low Range: 8.63
High Range: 11.50
4. Extensive motor and drive testing on these units ensures that the
full horsepower and watts range of the motor can be utilized with
confidence. Using the fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor fail-
ure. Unit warranty will not be affected.
5. Use of a field-supplied motor may affect wire size. Contact the
Bryant representative for details.
23
0.8
1.0
Watts
Bhp
Rpm
Watts
3,400
3.91
959
3,692
3,954
4.55
1000
4,245
4,575
5.26
1043
4,868
5,265
6.06
1088
5,564
6,025
6.93
1134
6,332
6,856
7.89
1181
7,173
7,761
8.93
1229
8,091
8,741
10.05
1278
9,086
9,799
11.27
1327
10,158
10,937
12.58
1376
11,311
1.8
2.0
Watts
Bhp
Rpm
Watts
5,195
5.97
1192
5646
5,685
6.54
1214
6122
6,261
7.20
1240
6680
6,928
7.97
1270
7329
7,684
8.84
1304
8071
8,527
9.81
1341
8905
9,457
10.88
1381
9830
10,474
12.05
Bhp
4.25
4.88
5.60
6.40
7.28
8.25
9.31
10.45
11.68
13.01
Bhp
6.49
7.04
7.68
8.43
9.28
10.24
11.31

Advertisement

Table of Contents
loading

Table of Contents