VOLTAGE
NOMINAL
581A
RANGE
VOLTAGE
No. 1
UNIT
(3 Ph,
SIZE
Min
Max RLA LRA RLA LRA RLA LRA Qty
60 Hz)
208/230
187
253
16.7
210
460
414
506
9
575
518
633
7
208/230
187
253
22.4
240
460
414
506
10.7
575
518
633
9.3
208/230
187
253
47.1
300
460
414
506
19.6
575
518
633
15.8
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Table 4A — Electrical Data — Units Without Convenience Outlet
COMPRESSOR
No. 2
No. 3
130
16.7
130
22.4
184
4
70
9
70
10.7
90
4
55
7
55
9.3
73
4
184
22.4
184
22.4
184
4
90
10.7
90
10.7
90
4
73
9.3
73
9.3
73
4
245
47.1
245
6
125
19.6
125
6
100
15.8
100
6
POWER
OFM
IFM
EXHAUST
FLA
Qty Hp FLA
Hp
Hp
FLA
(ea)
3.7
10.6/ 9.6
2
1
0.25
1.5
5
16.7/15.2
2
1
3.7
4.8
2
1
0.25
0.7
5
7.6
2
1
3
3.9
2
1
0.25
0.7
5
6.1
2
1
5
16.7/15.2
2
1
0.25
1.5
7.5
24.2/22
2
1
5
7.6
2
1
0.25
0.7
7.5
11
2
1
5
6.1
2
1
0.25
0.7
7.5
9
2
1
7.5
24.2/22
2
1
0.25
1.5
10
30.8/28
2
1
7.5
11
2
1
0.25
0.7
10
14
2
1
7.5
9
2
1
0.25
0.7
10
11
2
1
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact the
local electric utility company immediately.
3. The convenience outlet full load amps (FLA) are 5, 3, and 3 for 208/230, 460,
575-V units, respectively.
13
COMBUSTION
POWER SUPPLY
FAN MOTOR
FLA
MCA
MOCP*
(ea)
78/ 77 100/ 90
5.9
90/ 89 100/100
0.5
84/ 83 100/100
5.9
96/ 94 100/100
39
45
3.1
45
50
0.3
42
50
3.1
48
50
32
40
2.4
37
45
0.24
35
40
2.4
39
45
96/ 94 100/100
5.9
107/106 125/125
0.5
103/101 125/110
5.9
115/113 125/125
45
50
3.1
51
60
0.3
49
50
3.1
55
60
39
45
2.4
44
50
0.24
42
50
2.4
47
50
139/137 175/175
5.9
151/149 175/175
0.5
146/143 175/175
5.9
158/155 200/200
59
60
3.1
66
80
0.3
62
80
3.1
69
80
49
60
2.4
54
60
0.24
51
60
2.4
56
60
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
7
457
= 1.53%
DISCONNECT
SIZE
FLA
83/ 82
97/ 96
90/ 89
104/102
42
49
45
52
35
40
37
43
103/102
117/115
112/109
126/123
49
56
53
60
42
48
46
51
147/144
160/158
154/151
168/164
63
70
66
73
52
57
54
59