K. Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a
single location.
L. Motors:
1. Compressor motors shall be of the refrigerant-cooled
type with line-break thermal and current overload
protection.
2. All fan motors shall have permanently lubricated bear-
ings, and inherent, automatic reset, thermal overload
protection.
3. Condenser-fan motor shall be totally enclosed.
M. Special Features:
1. Louvered Grille:
Wire grille shall be standard on all units. Louvered
grille shall be available as a factory-installed option
to provide hail guard and vandalism protection.
2. Coil Options:
Shall include factory-installed optional copper/copper
and vinyl-coated refrigerant coils.
3. Economizer:
a. Economizer controls capable of providing free
cooling using outside air.
b. Equipped with low leakage dampers not to
exceed 3% leakage, at 1.0 in. wg pressure
differential.
c. Spring return motor shuts off outdoor damper on
power failure.
4. Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for
flashing and shall be installed per manufacturer's
instructions.
5. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and
rainhood which can be preset to admit outdoor air for
year-round ventilation.
6. Thermostat:
To provide for one-stage heating and cooling in ad-
dition manual or automatic changeover and indoor
fan control.
Heating & Cooling Systems
© 2000 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231
GUIDE SPECIFICATIONS (cont)
10. Controls Upgrade Kit:
11. Square-To-Round Duct Transitions:
12. Compressor Protection:
13. Duct Conversion Kit:
14. Crankcase Heater:
15. High-Altitude Kit:
16. Low NO :
17. Compressor Hard Start Kit:
24
7. Natural-to-Propane Conversion Kit:
Shall be complete with all required hardware to con-
vert to liquid propane (LP) operation at 3.5 in. wg
manifold pressure.
8. Low Ambient Package:
Shall consist of a solid-state control and condenser
coil temperature sensor for controlling condenser-fan
motor operation, which shall allow unit to operate
down to 0 F outdoor ambient temperature.
9. Filter Rack Kit:
Shall provide filter mounting for downflow
applications.
Shall provide high and low pressure safety
protection.
Shall have the ability to convert the supply and return
openings from rectangular to round.
Solid-state control shall protect compressor by pre-
venting "short cycling."
Shall enable conversion of a factory-supplied side
discharge unit to horizontal discharge airflow unit.
Shall provide anti-floodback protection for low-load
cooling applications.
Shall consist of natural gas orifices to compensate
for gas heat operation at 2001 to 4500 ft above sea
level.
x
Shall provide NO
reduction to values below
x
40 nanograms/joule to meet California emission
requirements as shipped from the factory.
Shall provide additional starting torque for single-
phase compressors.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
Printed in U.S.A.
WITH INSTALLATION INSTRUCTIONS
Cancels PDS 582.18.1
3-00