Electrical Data - Bryant 582A User Manual

Single-package gas heating/electric cooling units
Table of Contents

Advertisement

UNIT
SIZE
V-PH-Hz
582A
018
208/230-1-60
024
208/230-1-60
208/230-1-60
030
208/230-3-60
208/230-1-60
036
208/230-3-60
460-3-60
208/230-1-60
042
208/230-3-60
460-3-60
208-230/1/60
048
208/230-3-60
460-3-60
208/230-1-60
060
208/230-3-60
460-3-60
LEGEND
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse . The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage

ELECTRICAL DATA

VOLTAGE
COMPRESSOR
RANGE
Min
Max
RLA
187
253
9.0
187
253
12.8
187
253
14.4
187
253
8.3
187
253
15.1
253
187
10.9
506
5.8
414
187
253
18.6
187
253
10.7
414
506
5.3
197
253
25.3
187
253
14.6
414
506
7.3
187
253
28.9
187
253
18.6
414
506
8.5
®
COND FAN
INDOOR FAN
MOTOR
LRA
FLA
45.0
0.8
61.0
0.8
73.0
0.8
68.0
0.8
81.0
1.6
78.0
1.6
40.0
0.9
105.0
1.6
85.0
1.6
42.0
0.9
131.0
1.6
108.0
1.6
47.5
0.9
147.0
1.6
125.0
1.6
66.5
0.9
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457
452 = 5 v
(BC) 464
457 = 7 v
(AC) 457
455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
21
POWER SUPPLY
MOTOR
FLA
MCA
1.8
13.9
2.0
18.8
2.0
20.8
13.2
2.0
24.1
3.6
3.6
18.8
10.1
1.9
3.8
28.9
3.8
18.8
2.0
9.5
3.8
37.0
3.8
23.7
2.0
12.0
6.2
43.9
6.2
31.1
3.2
14.7
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
1371
=
3
= 457
7
457
= 1.53%
MOCP*
20
30
30
20
35
25
15
45
25
15
60
35
15
60
45
20
3