FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont)
580D072 (6 TONS)*
Airflow
0.1
(Cfm)
Rpm
Bhp
Watts
1800
885
0.63
623
1900
928
0.73
700
2000
971
0.84
787
2100
1015
0.97
891
2200
1060
1.10
998
2300
1104
1.25
1123
2400
1138
1.30
1165
2500
1183
1.43
1275
2600
1210
1.58
1404
2700
1254
1.76
1560
2800
1274
1.82
1613
2900
1318
1.95
1726
3000
1362
2.20
1945
580D072 (6 TONS)* (cont)
External Static Pressure (in. wg)
Airflow
1.2
(Cfm)
Rpm
Bhp
Watts
1800
1341
1.40
1250
1900
1374
1.53
1361
2000
1396
1.66
1473
2100
1413
1.75
1552
2200
1434
1.81
1604
2300
1459
1.88
1665
2400
1502
2.06
1823
2500
1524
2.24
1980
2600
1552
2.40
2119
2700
1584
2.61
2300
2800
1624
2.85
2504
2900
1671
3.03
2725
3000
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range is 1070 to 1460 rpm. All other rpms require a field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See
page 52 for accessory/FIOP static pressure information.
PERFORMANCE DATA (cont)
External Static Pressure (in. wg)
0.2
Rpm
Bhp
Watts
Rpm
942
0.73
700
1047
982
0.83
779
1084
1022
0.94
867
1121
1063
1.10
998
1140
1104
1.20
1081
1159
1130
1.27
1140
1196
1174
1.37
1224
1245
1201
1.50
1335
1284
1246
1.67
1482
1312
1285
1.80
1595
1354
1304
1.85
1639
1374
1345
2.05
1814
1412
1378
2.30
2032
1451
1.4
Rpm
Bhp
Watts
Rpm
Bhp
1413
1.55
1378
1474
1.58
1437
1.62
1439
1490
1.67
1460
1.68
1491
1509
1.77
1475
1.73
1534
1529
1.92
1487
1.85
1639
1554
2.07
1520
2.07
1831
1576
2.24
1552
2.24
1980
1604
2.42
1585
2.42
2136
1638
2.60
1616
2.63
2317
1671
2.80
1646
2.83
2487
1706
2.97
1677
2.99
2661
0.4
0.6
Bhp
Watts
Rpm
Bhp
Watts
0.90
835
1139
1.05
1.02
932
1160
1.11
1006
1.12
1014
1188
1.22
1097
1.18
1064
1196
1.27
1140
1.23
1106
1229
1.41
1258
1.37
1224
1264
1.56
1387
1.57
1396
1305
1.63
1447
1.65
1465
1338
1.75
1552
1.76
1560
1366
1.96
1735
1.95
1726
1403
2.14
1892
2.12
1875
1459
2.25
1989
2.32
2050
1496
2.54
2240
2.40
2119
1534
2.66
2343
1.6
Watts
1404
1482
1569
1700
1831
1980
2136
2292
2462
2653
3. Maximum continuous bhp is 2.4 and maximum continuous watts are
2120. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. See Evaporator-Fan Motor Performance table on page 55
for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
5. Interpolation is permissible. Do not extrapolate.
42
0.8
Rpm
Bhp
Watts
Rpm
956
1193
1.14
1031
1276
1223
1.24
1114
1301
1254
1.36
1216
1329
1272
1.45
1292
1354
1306
1.53
1361
1363
1340
1.66
1473
1397
1373
1.84
1630
1440
1402
1.99
1761
1469
1435
2.10
1858
1494
1474
2.21
1954
1536
1514
2.42
2136
1570
1529
2.61
2300
1603
1560
2.81
2470
1611
1.0
Bhp
Watts
1.30
1165
1.38
1233
1.44
1284
1.58
1404
1.70
1508
1.86
1648
1.95
1726
2.04
1805
2.19
1936
2.46
2171
2.66
2343
2.87
2521
3.01
2648