Bryant 580D Product Information Manual page 36

Commercial single package rooftop gas heating/electric cooling units 3 to 25 tons
Table of Contents

Advertisement

FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont)
580D102 (8
1
TONS)*
2
Airflow
0.2
(Cfm)
Rpm
Bhp
2550
559
0.72
2600
567
0.75
2700
582
0.83
2800
598
0.90
2900
614
0.98
3000
630
1.07
3100
646
1.16
3200
662
1.26
3300
679
1.36
3400
695
1.47
3500
712
1.59
3600
729
1.71
3700
745
1.84
3750
754
1.91
3800
762
1.98
3900
779
2.12
4000
796
2.27
4100
813
2.42
4200
830
2.59
4250
839
2.68
580D102 (8
1
TONS)* (cont)
2
Airflow
1.2
(Cfm)
Rpm
Bhp
2550
864
2.01
2600
869
2.06
2700
880
2.17
2800
892
2.29
2900
903
2.42
3000
915
2.54
3100
926
2.67
3200
938
2.81
3300
950
2.95
3400
963
3.10
3500
976
3.25
3600
988
3.41
3700
3750
3800
3900
4000
4100
4200
4250
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range is 685 to 935 rpm. All other rpms require a field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See
page 52 for accessory/FIOP static pressure information.
PERFORMANCE DATA (cont)
0.4
Watts
Rpm
Bhp
Watts
692
634
0.97
891
716
641
1.00
916
779
655
1.08
981
835
670
1.17
1056
899
684
1.25
1123
973
690
1.35
1207
1047
714
1.45
1292
1131
729
1.55
1378
1216
744
1.66
1473
1310
759
1.78
1578
1413
774
1.90
1683
1517
790
2.03
1796
1630
805
2.17
1919
1691
813
2.24
1980
1753
821
2.31
2041
1875
836
2.46
2171
2006
852
2.61
2300
2136
868
2.78
2445
2283
884
2.95
2587
2360
890
3.04
2661
External Static Pressure (in. wg)
1.4
Watts
Rpm
Bhp
Watts
1779
915
2.34
2067
1823
918
2.37
2093
1919
927
2.47
2180
2023
938
2.58
2275
2136
949
2.71
2386
2240
961
2.85
2504
2352
972
3.00
2629
2470
983
3.14
2743
2587
995
3.30
2870
2710
1007
3.45
2987
2831
2956
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
700
1.21
1089
706
1.25
1123
719
1.34
1199
732
1.43
1275
745
1.53
1361
759
1.63
1147
773
1.74
1543
787
1.86
1648
801
1.98
1753
816
2.10
1858
830
2.23
1971
845
2.37
2093
860
2.52
2223
868
2.59
2283
875
2.66
2343
890
2.82
2479
905
2.98
2612
920
3.15
2751
935
3.33
2894
1.6
Rpm
Bhp
Watts
968
2.81
2479
973
2.81
2487
976
2.84
2495
983
2.92
2562
993
3.03
2653
1003
3.17
2767
1016
3.32
2886
1026
3.47
3002
3. Maximum continuous bhp is 2.4 and maximum continuous watts are
2120. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. See Evaporator-Fan Motor Performance table on page 55
for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
5. Interpolation is permissible. Do not extrapolate.
36
0.8
Rpm
Bhp
Watts
Rpm
759
1.48
1318
814
764
1.52
1353
819
776
1.61
1430
831
789
1.71
1517
842
802
1.81
1604
854
815
1.92
1700
866
828
2.04
1805
878
841
2.16
1910
891
854
2.29
2023
904
867
2.42
2136
917
881
2.56
2257
930
895
2.71
2386
943
909
2.87
2521
956
917
2.95
2587
963
924
3.03
2653
970
938
3.19
2783
953
3.37
2925
1.0
Bhp
Watts
1.74
1543
1.79
1587
1.89
1674
2.00
1770
2.11
1866
2.23
1971
2.35
2076
2.48
2188
2.61
2300
2.75
2420
2.90
2546
3.05
2670
3.22
2807
3.30
2870
3.38
2933

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents