Bryant PREFERRED 265A Product Data
Bryant PREFERRED 265A Product Data

Bryant PREFERRED 265A Product Data

Preferred series heat pump with puron refrigerant
Hide thumbs Also See for PREFERRED 265A:

Advertisement

MODEL 265A
PREFERRED™ SERIES HEAT PUMP
WITH PURON® REFRIGERANT
SIZES 018 TO 060
1- -1/2 TO 5 NOMINAL TONS
Bryant's heat pumps with Puronr refrigerant provide a collection
of features unmatched by any other family of equipment. The
265A has been designed utilizing Bryant's Puronr refrigerant.
The environmentally sound refrigerant allows consumers to make
a responsible decision in the protection of the earth's ozone layer.
As an Energy Starr Partner, Bryant Heating & Cooling Systems
has determined that this product meets the Energy Star r
guidelines for energy efficiency. Refer to the combination ratings
in the Product Data for system combinations that meet Energy
Starr guidelines.

Product Data

INDUSTRY LEADING
FEATURES / BENEFITS
Energy Efficiency
S
New Aesthetic Design
S
S
S
S
Extra Quiet Operation
S
S
S
S
TM
S
S
S
S
Reliability, Quality and Toughness
S
S
S
S
S
S
S
S
S
Controls and Diagnostics
S
S
S
S
Applications
S
S

Limited Warranty

S
S
15 SEER/11.5 EER/8 HSPF (Nominal)
DuraGuard Ultrat
Baked on powder paint
Steel louver coil guard
Color matched cabinet screws
AeroQuiet System IIt for sound as low as 69 dBA
Quiet mount split post compressor grommets
External AeroQuiet muffler
Exclusive AeroQuiet Top design
8 Pole PSC ball bearing condenser fan motor
Forward- -swept condenser fan blade
Compressor blanket
Quiet shift defrost
Scroll compressor
Field- -installed 16 cu. in. filter drier
Back- -seating service valves
High pressure switch
Loss of charge switch
Internal pressure relief valve
Internal thermal overload
Suction line accumulator
Vapor fog eliminator
Evolutiont control compatible
On- -board Bryant diagnostics
Up to 14 point diagnostic capability·
Long line accessory connections
Long- -line - - up to 250 ft. total equivalent length, up to
200 ft. condenser above evaporator, or up to 20 ft.
evaporator above condenser standard, (50 ft. w/liquid
line solenoid)
Low ambient (down to 0_F) with Evolutiont Control
or accessory kit.
Standard 10- -year limited warranty on the compressor
Standard 5- -year limited warranty on all parts

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PREFERRED 265A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bryant PREFERRED 265A

  • Page 1: Product Data

    The environmentally sound refrigerant allows consumers to make a responsible decision in the protection of the earth’s ozone layer. As an Energy Starr Partner, Bryant Heating & Cooling Systems has determined that this product meets the Energy Star r guidelines for energy efficiency. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines.
  • Page 2: Model Number Nomenclature

    0=Not 0=Not Defined Defined Defined As an Energy Star® Partner, Bryant Heating & Cooling Systems has determined that this product meets the ENERGY STAR® guidelines for energy efficiency. Refer to the combination ratings in Product Data for system combinations that meet Energy Star guidelines.
  • Page 3: Physical Data

    * For tubing sets between 80 ft. and 200 ft. horizontal or 20 ft. vertical differential (250 ft. Total Equivalent Length), consult the Long---Line Guideline. Note: See unit Installation Instruction for proper installation. VAPOR LINE SIZING AND COOLING CAPACITY LOSS PURON 1- -STAGE HEAT PUMP APPLICATIONS LONG LINE APPLICATION: An application is considered ”Long line” when the total equivalent tubing length exceeds 80 ft.
  • Page 4: Accessory Thermostats

    * Do not use in zoning heat pump applications. ** Outdoor temperature sensor is an accessory for all Bryant electronic thermostats, except the non ---programmable air conditioner version and builder;s thermostats. It allows the temperature at a remote location (outdoors) to be displayed on the thermostat. The outdoor air temperature sensor must be used with the HybridHeatt (dual fuel) thermostat.
  • Page 5: Accessory Usage Guideline

    Guideline Standard 6. Isolation Relay An SPDT relay which switches the low- -ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode. Usage Guideline: is used. Required in all heat pumps where low ambient kit has been added.
  • Page 6 Accessory Description and Usage (Listed Alphabetically) - - CONTINUED 10. Outdoor Air Temperature Sensor Designed for use with Bryant Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also is required to enable special thermostat features such as auxiliary heat lock out.
  • Page 7: Electrical Data

    ELECTRICAL DATA OPER VOLTS* UNIT SIZE V/PH 018---B 024---B 030---B 036---B 208/230/1 042---B 048---B 060---B * Permissible limits of the voltage range at which the unit will operate satisfactorily { If wire is applied at ambient greater than 30° C (86° F), consult table 310 ---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60°...
  • Page 9 MBTUH CAPACITY, INTEGRATED UNIT LOSS, HEAT HEATING BUILDING...
  • Page 10: Combination Ratings

    COMBINATION RATINGS Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance *FX4CNF018 17,800 TDR&TXV FE4ANF002 18,000 TDR&TXV FF1ENP018 17,400 TDR&TXV FF1ENP024 17,700 TDR&TXV FV4BNF002 18,000 TDR&TXV FX4CNF024 18,000 TDR&TXV FY4ANF018 17,400 TDR&TXV FY4ANF024 17,600 TDR&TXV CAP**1814A** 17,300 TDR&TXV CAP**1814A** 17,400 CAP**2414A** 17,600...
  • Page 11: Combination Ratings Continued

    COMBINATION RATINGS CONTINUED Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance CNPH*2417A** 23,000 TDR&TXV CNPH*2417A** 22,800 TDR&TXV CNPH*2417A** 23,000 TDR&TXV CNPH*2417A** 22,800 TDR&TXV CNPH*2417A** 23,000 TDR&TXV CNPH*2417A** 22,800 TDR&TXV CNPH*2417A** 23,000 CNPH*3017A** 23,200 TDR&TXV CNPH*3017A** 23,200 TDR&TXV CNPH*3017A** 23,200 TDR&TXV CNPH*3017A**...
  • Page 12 COMBINATION RATINGS CONTINUED Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance CAP**3017A** 28,800 TDR&TXV CAP**3017A** 28,800 TDR&TXV CAP**3017A** 29,000 CAP**3614A** 27,800 TDR&TXV CAP**3614A** 28,000 CAP**3617A** 29,000 TDR&TXV CAP**3617A** 28,800 TDR&TXV CAP**3617A** 29,000 CAP**3621A** 29,000 TDR&TXV CAP**3621A** 29,000 TDR&TXV CAP**3621A** 29,000 TDR&TXV...
  • Page 13 COMBINATION RATINGS CONTINUED Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance CSPH*3612A** 29,000 TDR&TXV CSPH*3612A** 29,000 TDR&TXV CSPH*3612A** 29,000 TDR&TXV CSPH*3612A** 28,800 TDR&TXV CSPH*3612A** 28,800 TDR&TXV 030- -B CSPH*3612A** 28,800 TDR&TXV CSPH*3612A** 28,800 TDR&TXV CSPH*3612A** 29,000 TDR&TXV CSPH*3612A** 29,000 TDR&TXV CSPH*3612A**...
  • Page 14 COMBINATION RATINGS CONTINUED Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance CNPH*4221A** 34,600 TDR&TXV CNPH*4221A** 34,800 TDR&TXV CNPH*4221A** 34,800 TDR&TXV 036- -B CNPH*4221A** 34,800 TDR&TXV CNPH*4221A** 34,800 TDR&TXV CNPH*4221A** 34,800 TDR&TXV CNPH*4221A** 35,000 CNPV*3617A** 34,400 TDR&TXV CNPV*3617A** 34,400 TDR&TXV CNPV*3617A** 34,600...
  • Page 15 COMBINATION RATINGS CONTINUED Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance CAP**4821A** 41,500 TDR&TXV CAP**4821A** 41,000 TDR&TXV CAP**4821A** 41,500 TDR&TXV CAP**4821A** 41,500 TDR&TXV CAP**4821A** 41,500 CAP**4824A** 41,500 TDR&TXV CAP**4824A** 41,500 TDR&TXV CAP**4824A** 41,000 TDR&TXV CAP**4824A** 41,500 TDR&TXV CAP**4824A** 41,500 CNPF*4818A** 40,500...
  • Page 16 COMBINATION RATINGS CONTINUED Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance CSPH*4812A** 41,500 TDR&TXV CSPH*4812A** 41,500 TDR&TXV CSPH*4812A** 41,000 TDR&TXV CSPH*4812A** 41,000 TDR&TXV 042- -B CSPH*4812A** 41,000 TDR&TXV CSPH*4812A** 41,500 TDR&TXV CSPH*4812A** 41,500 TDR&TXV CSPH*4812A** 41,500 TDR&TXV CSPH*4812A** 41,500 048- -B *FX4CN(B,F)060...
  • Page 17 COMBINATION RATINGS CONTINUED Unit Size Cooling Indoor Model --- Series Capacity Factory Enhance CSPH*4812A** 47,000 TDR&TXV CSPH*4812A** 47,000 TDR&TXV CSPH*4812A** 47,500 TDR&TXV CSPH*4812A** 47,500 TDR&TXV CSPH*4812A** 47,000 TDR&TXV CSPH*4812A** 47,000 TDR&TXV CSPH*4812A** 47,000 TDR&TXV CSPH*4812A** 48,000 048- -B CSPH*6012A** 48,000 TDR&TXV CSPH*6012A** 48,000...
  • Page 18: Detailed Cooling Capacities

    DETAILED COOLING CAPACITIES EVAPORATOR Total Capacity Capacity Sys- MBtuh† MBtuh† Sens Total Total ‡ 21.38 11.04 1.16 20.36 19.39 13.53 1.16 18.44 17.97 13.07 1.17 17.08 17.61 16.02 1.17 16.74 16.98 16.98 1.17 16.29 21.85 11.59 1.17 20.79 19.82 14.40 1.17 18.83 18.37...
  • Page 19 DETAILED COOLING CAPACITIES CONTINUED EVAPORATOR Total Capacity Capacity Sys- MBtuh† MBtuh† Sens Total Total ‡ 28.21 14.49 1.47 26.92 25.60 17.78 1.46 24.41 23.74 17.18 1.46 22.61 23.27 21.07 1.46 22.17 22.41 22.41 1.46 21.53 28.81 15.19 1.49 27.47 26.16 18.90 1.49 24.91...
  • Page 20 DETAILED COOLING CAPACITIES CONTINUED EVAPORATOR Total Capacity MBtuh Capacity MBtuh Sys- Total Sens Total 34.91 18.12 1.82 33.33 31.70 22.36 1.82 30.24 29.41 21.58 1.82 28.03 28.84 26.56 1.82 27.51 27.97 27.97 1.82 26.90 35.59 18.98 1.85 33.96 32.32 23.74 1.85 30.80 1000...
  • Page 21 DETAILED COOLING CAPACITIES CONTINUED EVAPORATOR Total Capacity Capacity Sys- MBtuh† MBtuh† Sens Total Total ‡ 42.99 22.20 2.25 41.05 39.02 27.33 2.23 37.23 1050 36.20 26.40 2.22 34.51 35.49 32.46 2.22 33.85 34.32 34.32 2.21 33.01 43.88 23.28 2.29 41.86 39.84 29.07 2.27...
  • Page 22 DETAILED COOLING CAPACITIES CONTINUED EVAPORATOR Total Capacity Capacity Sys- MBtuh† MBtuh† Sens Total Total ‡ 50.45 25.64 2.53 47.95 46.02 31.77 2.61 43.73 1225 42.74 30.73 2.67 40.63 41.89 37.84 2.68 39.83 40.32 40.32 2.70 38.70 51.34 26.80 2.57 48.73 46.88 33.73 2.66...
  • Page 23 DETAILED COOLING CAPACITIES CONTINUED EVAPORATOR Total Capacity Capacity Sys- MBtuh† MBtuh† Sens Total Total ‡ 57.47 29.60 2.93 54.70 52.33 36.48 2.94 49.77 1400 48.56 35.25 2.95 46.18 47.58 43.31 2.95 45.25 45.92 45.92 2.95 44.08 58.63 31.04 2.97 55.74 53.44 38.83 2.98...
  • Page 24 DETAILED COOLING CAPACITIES CONTINUED EVAPORATOR Total Capacity Capacity Sys- MBtuh† MBtuh† Sens Total Total ‡ 71.33 36.68 4.31 67.94 65.68 45.79 4.24 62.55 1750 61.47 44.48 4.19 58.52 60.32 54.79 4.18 57.45 58.31 58.31 4.16 55.99 72.40 38.30 4.40 68.88 66.76 48.55 4.34...
  • Page 32: Guide Specifications General

    GUIDE SPECIFICATIONS GENERAL System Description Outdoor- -mounted, air- -cooled, split- -system heat pump unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, air- -cooled condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.