Technical Data - S+S Regeltechnik AERASGARD RFTM-PS Series Operating Instructions, Mounting & Installation

Multifunctional room sensor and measuring transducer for humidity, temperature, fine dust (pm) and c02 content, calibratable. with active /switching output
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 10
G
®
AERASGARD
RPS - SD ⁄ RFTM - PS - xx
Maintenance-free room sensor AERASGARD
ment, for detecting the fine dust content (0...500 µg/m
Maintenance-free, multifunctional room sensor AERASGARD
plastic housing with snap-on lid, base with 4-hole attachment, optionally with/without display, for detection of measurands air humidity (0...100 % r.H.),
temperature (0...+50°C), fine dust (PM) (0...50 / 100 / 300 / 500 µg/m
the measurand into a standard signal of 0 -10 V or 4...20 mA (switchable).
Use just one device to monitor and control the entire indoor climate effectively. This enables energy-saving room ventilation on an as-needed basis,
thereby reducing operating costs and improving well-being. It is used in offices, hotels, convention centres, apartments, shops, etc. We recommend
one sensor for every 30 m² of space.
A long-term stable, digital humidity and temperature sensor guarantees exact measurement results. The CO2 content of the air is measured using
an optical NDIR sensor (non-dispersive infra-red technology). An optical particulate sensor precisely detects fine dust (PM) of the size category 0.3
to 10 micrometers. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible. (except for particulate sensor)

TECHNICAL DATA

Power supply:
Power consumption:
Output:
Relay output:
HUMIDIT Y
Sensor (RH / °C):
Measuring range (RH):
Output (RH):
Deviation (RH):
TEMPERATURE
Measuring range (°C):
Output (°C):
Deviation (°C):
FINE DUST ( PM )
Sensor (PM):
Measuring range (PM):
Output (PM):
Particle size (PM):
Measuring accuracy (PM):
Long-term stability (PM):
Service life (PM):
CARBON DIOXIDE ( CO2 )
Sensor (CO2):
Measuring range (CO2):
Output (CO2):
Measuring accuracy (CO2):
Temperature dependence (CO2):
Pressure dependence (CO2):
Long-term stability (CO2):
Gas exchange (CO2):
®
RPS - SD with active output, in an elegant plastic housing with snap-on lid, base with 4-hole attach-
3
). The measuring transducer converts the measurand into a standard signal of 0 -10 V (fixed).
®
RFTM - PS - CO2 - W with active/switching output, automatic calibration, in an elegant
24 V AC ⁄ DC (± 10 %)
RPS - SD
typically < 1.5 W ⁄ 24 V DC; < 2.9 VA ⁄ 24 V AC
typically < 4.4 W ⁄ 24 V DC; < 6.4 VA ⁄ 24 V AC; peak current 200 mA
RFTM - PS - CO2 - W
RPS - SD
0 -10 V (fixed)
0 -10 V or 4...20 mA, working resistance < 800 Ω
RFTM - PS - CO2 - W
(selectable via DIP switches, selected version applies uniformly to all outputs),
with offset potentiometer (± 10 % of measuring range)
RPS - SD
without changeover contact
with potential-free changeover contact (24 V / 1 A)
RFTM - PS - CO2 - W
(assignment selectable via DIP switches, switch point can be set)
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
0...100 % r. H.
0 -10 V or 4...20 mA (selectable via DIP switches)
typically ± 2.0 % (20...80 % r. H.) at +25 °C, otherwise ± 3.0 %
0...+ 50 °C
0 -10 V or 4...20 mA (selectable via DIP switches)
typically ± 0.2 K at +25 °C
optical fine-dust sensor (PM = particulate matter),
particulate sensor with laser- and soiling-resistant technology
multi-range switching (selectable via DIP switches)
0...50, 0...100, 0...300 or 0...500 µg/m
RPS - SD
0 -10 V (fixed)
0 -10 V or 4...20 mA (selectable via DIP switches)
RFTM - PS - CO2 - W
PM 2.5 (0.3...2.5 µm); PM 10 (0.3...10 µm)
typically ± 10 µg/m
3
(± 10 % of measured value) at PM 2.5
typically ± 25 µg/m
3
(± 25 % of measured value) at PM 10
3
± 1.25 µg/m
(± 1.25 % of measured value/year)
> 10 years
Optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button),
with automatic calibration (can be deactivated via DIP switches)
0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
0 -10 V or 4...20 mA (selectable via DIP switches)
typically ± 30 ppm (± 3 % of measured value)
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is greater)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
Diffusion
3
) and CO2 content (0...2000 / 5000 ppm). The measuring transducer converts
3
10
Rev. 2021 - V11
Continued on next page!