Technical Data - S+S Regeltechnik HYGRASREG AH-30W Operating Instructions, Mounting & Installation

On-wall hygrostat and humidity sensor, electronic, two-step and with active output
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
®
HYGRASREG
AH - 30
Electronic on-wall hygrostat and humidity sensor HYGRASREG
thresholds, optional with or without display indicating the actual humidity, accuracy class ± 3 % r.H. It is used to control and monitor the rela-
tive humidity, e.g. in venti lation and air conditioning ducts, laboratories, production facilities, climatic test cabinets, indoor swimming pools,
greenhouses, etc. to control humidifying and dehumidifying equipment. This measuring transducer is designed for exact humidity measure-
ment.

TECHNICAL DATA:

Power supply: .............................. 24 V AC ⁄ DC (optional 230 V AC via external power supply unit)
Setting range: ............................ 5 ... 95 % r. H. (switch steps 1 and 2 are separately adjustable)
Operating difference: ................ Mode 1: both switch steps are arbitrary adjustable
Output: ......................................... potential-free changeover contact
Sensors: ....................................... digital humidity sensor
Deviation, humidity: .................... ± 3 % r. H. (20...90 %); at + 20 °C, otherwise ± 5 % r. H.
Long-term stability: .................... ± 1 % per year
Hysteresis: .................................. max. 3 % r. H.
Sensor protection: ..................... membrane filter, exchangeable
Enclosure temperature: ............ - 10 °C ...+ 65 °C
Enclosure: .................................... plastic, material polyamide, 30 % glass-globe-reinforced,
Dimensions: ................................. 108 x 72,5 x 70 mm
Cable gland: ................................. M16, including strain relief
Flow rate: ..................................... max. 8 m ⁄ s
Protective tube: .......................... metal, Ø 20 mm, NL = 103 mm
Protection class: ........................ I (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529)
Electrical connection: ............... 0.14 - 2.5 mm
Standards: ................................... CE conformity, EMC directive 2004 ⁄ 108 ⁄ EC
Optional: ....................................... Single-line display, shifting, 36 x15 mm (W x H),
FUNCTION:
Humidifying: ................................. 1
Dehumidifying: ............................ 1
Type ⁄ WG2
Setting Range
Humidity (relative)
AH - 30 W
5 ... 95 % r. H.
AH - 30 W - Display
5 ... 95 % r. H.
Optional:
for 230 V AC supply voltage via external power supply unit
Mode 2: 5 % between both switch steps
(2 x changeover contact 24 V, separately adjustable, 1x 0 - 10 V ^ = 0 - 100 % r. H.)
with quick-locking screws, colour pure white (similar RAL 9010)
2
, via terminal screws
for displaying ACTUAL humidity respectively
for humidity setpoint adjustment
st
step: wire contacts 4 - 5.
When actual humidity falls more than 3 % r. H. (hysteresis)
below switching threshold S1,
changeover contact switches to 4 - 5.
2
nd
step: wire contacts 7 - 8.
When actual humidity falls more than 3 % r. H. (hysteresis)
below switching threshold S 2,
changeover contact switches to 7 - 8.
Terminal 2: 1x 0 - 10 V equivalent to 0...100 % r. H.
st
step: wire contacts 5 - 6.
When actual humidity exceeds switching threshold S 1,
changeover contact switches to 5 - 6.
nd
2
step: wire contacts 8 - 9.
When actual humidity exceeds switching threshold S 2,
changeover contact switches to 8 - 9.
Terminal 2: 1x 0 - 10 V ^ = 0 - 100 % r. H.
Steps
2
2
®
AH-30 with one continuous and two switching outputs, adjustable switching
Output
2 x changeover contact, 1 x 0 -10 V
2 x changeover contact, 1 x 0 -10 V
Features
Internal setting
Internal setting, display

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hygrasreg ah-30w-display

Table of Contents