"Sc" - Combustion Control Parameters Menu
ONLY QUALIFIED PERSONNEL CAN ACCESS THE "SC" MENU AND MODIFY THE RELEVANT PARAMETERS.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to
view or modify the value of a parameter. To save the edited parameter press either the heating"+" or "-" button (details
3 and 4 - fig. 1).
Contents
Description
Sc01
Gas type selection
Sc02
Ignition gas setting
Sc03
Ignition power
Sc04
Flue length
Sc05
Minimum power setting
Sc06
Minimum gas valve setting
Sc07
Flame ionization signal
Sc08
Current power ref. DHW
Sc09
MAX ionization value
Sc10
Minimum ionization value during ignition
Sc11
Ignition time
Sc12*
Ionization reduction value (BASE)
Sc13**
Ionization reduction value (min.)
Sc14
Internal error K1
Sc15
100% CALIBRATION
Sc16
Parameter loading with "KEY" device
PARAMETERS "SC12" AND "SC13" MUST BE MODIFIED, IF STRICTLY NECESSARY, BY QUALIFIED PERSON-
NEL AND ONLY WHEN THE CO
on page 192. CARRY OUT THE PROCEDURE AFTER AT LEAST 500 HOURS OF BOILER OPERATION.
* SC12 regulates the CO
CO
decreases; by decreasing the parameter value the CO
2
174
BLUEHELIX TECH RRT 28 C
Functional description
Allows the change of gas type. See "Gas conversion" on
page 166
Allows the amount of gas to be increased or decreased in
the ignition phase in case of difficult starting.
Allows the fan speed to be increased or decreased in the
ignition phase in case of difficult starting.
Allows the boiler to be arranged according to the width
and length of the flue used. To be used only with Ø50 or
Ø60 flues. See fig. 25.
Allows the minimum power to be increased, if necessary. 0 ÷ 25
Self-adaptive parameter. DO NOT MODIFY.
Displays the actual ionization current signal.
Displays the actual power referred to maximum power in
DHW.
Displays the maximum ionization value reached.
Displays the minimum ionization value reached during the
ignition phase.
Displays the time from fan activation to ionization.
Allows the adjustment of CO
mum and minimum power, translating the entire value
curve.
Allows the adjustment of CO
Displays the SCOT system error code.
Allows 100% Calibration (see "100% calibration" on
page 167) when replacing some components (see
"Extraordinary maintenance and replacement of compo-
nents" on page 179)
Allows updating or restoring the circuit board parameters
(see "Loading parameters with KEY" on page 168)
VALUES ARE OUTSIDE THE RANGE INDICATED IN "- Technical data table"
2
at the same time at maximum and minimum power. By increasing the parameter value the
2
cod. 3541N260 - Rev. 01 - 10/2017
at the same time as maxi-
2
at minimum power.
2
increases.
2
Range
Default
na / LP
na
-9 ÷ 20
0
-16 -- 14
0
-5 ÷ 22
0
0
Read only
Read only
Read only
Read only
Read only
-5 ÷ 10
0
-5 ÷ 10
0
Read only
0 - CAL
0
EN