Contents Description
P33
Heating Post-Circulation
P34
Pump operation
P35
Modulating pump min. speed
P36
Modulating pump start speed
P37
Modulating pump max. speed
Pump deactivation temperature during Post-
Circulation (b01=1)
Pump deactivation temperature during Post-
Circulation (b01=2)
P38
Pump deactivation temperature during Post-
Circulation (b01=3)
Pump deactivation temperature during Post-
Circulation (b01=4)
Pump activation hysteresis temperature during
Post-Circulation (b01=1)
Pump activation hysteresis temperature during
Post-Circulation (b01=2)
P39
Pump activation hysteresis temperature during
Post-Circulation (b01=3)
Pump activation hysteresis temperature during
Post-Circulation (b01=4)
P40
Heating user max. setpoint
P41
Max. output in heating
Burner shutdown in DHW (b01=1)
Legionella protection (b01=2)
P42
Burner shutdown in DHW (b01=3)
Legionella protection (b01=4)
Comfort activation temperature (b01=1)
Hot water tank hysteresis (b01=2)
P43
Comfort activation temperature (b01=3)
Hot water tank hysteresis (b01=4)
Not used (b01=1)
Primary setpoint (b01=2)
P44
Comfort deactivation hysteresis (b01=3)
Primary setpoint (b01=4)
DHW standby time (b01=1)
DHW standby time (b01=2)
P45
DHW standby time (b01=3)
DHW standby time (b01=4)
DHW user max. setpoint (b01=1)
DHW user max. setpoint (b01=2)
P46
DHW user max. setpoint (b01=3)
DHW user max. setpoint (b01=4)
DHW pump Post-Circulation (b01=1)
DHW pump Post-Circulation (b01=2)
P47
DHW pump Post-Circulation (b01=3)
DHW pump Post-Circulation (b01=4)
P48
Max. output in DHW
Comfort1 standby time (b01=1)
Not implemented (b01=2)
P49
Not implemented (b01=3)
Not implemented (b01=4)
172
BLUEHELIX TECH RRT 28 C
Range
0-255 minutes
0-7=Operation strategy
0-100%
0-100%
0-100%
0-100°C
0-100°C
0-100°C
0-100°C
0-100°C
0-100°C
0-100°C
0-100°C
20-90°C
0-100%
0=Fixed, 1=Linked to setpoint, 2=Solar
0-7=Activation days
0=Fixed, 1=Linked to setpoint, 2=Solar
0-7=Activation days
0-50°C
0-60°C
0-80°C
0-60°C
Do not modify
70-85°C
0-20°C
70-85°C
30-255seconds
30-255seconds
30-255seconds
30-255seconds
40-70°C
40-70°C
40-70°C
40-70°C
0-255seconds
0-255seconds
0-255seconds
0-255seconds
0-100%
0-100minutes
--
--
--
cod. 3541N260 - Rev. 01 - 10/2017
Default
15 minutes
2
30%
90%
100%
50°C
55°C
55°C
55°C
10°C
25°C
25°C
25°C
80°C
80%
0=Fixed
0=No protection
0=Fixed
0=No protection
40°C
2°C
40°C
2°C
0
80°C
20°C
80°C
120seconds
120seconds
120seconds
120seconds
55°C
65°C
55°C
65°C
3seconds
30seconds
30seconds
30seconds
100%
20minutes
--
--
--
EN