ABB REJ 523 Technical Reference Manual page 61

Overcurrent relay
Table of Contents

Advertisement

ABB Substation Automation
Products and Systems
1MRS750940-MUM
Technical Reference Manual
Setting group 2
Variable
Start current of stage I>
Operate time or time
multiplier k of stage I>
Start current of stage I>>
Operate time of
stage I>>
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGB 1
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Control parameters
Variable
Rated frequency
Remote control of
settings
Event mask for I>
and I>>
Event mask for output
contacts' events
Event mask for
disturbance recorder
SPA address of the relay
Data transfer rate
Operate time of circuit-
breaker failure protection
Time setting for disabling
new trip indication on
LCD
Group 2
Setting
(R, W, P)
range
S81
0.30...5.00 x I
S82
0.05...300 s
S83
0.30...35.0 x I
S84
0.04...300 s
S85
0...255
S86
0...255
S87
0...255
S88
0...255
S89
0...255
S90
0...255
S91
0...255
S92
0...255
Parameter
Setting
range
V133
50 / 60
V150
0 / 1
V155
0...255
V156
0...255
V157
0 / 1
V200
1...254
V201
4.8 or 9.6
S121
0.10...1.00 s
S122
0...999 min
REJ 523
Default
Customer's
setting
0.30 x I
n
n
0.05 s /
0.05
0.30 x I
n
n
0.04 s
0
0
0
0
12
3
12
3
Default
Customer's
setting
50
0
85
3
1
1
9.6
0.10 s
60
setting
setting
61