Although the module RER 103 supports both SPA bus and LON bus communication,
the relay only allows the use of SPA bus. LON communication is possible with a
separate LSG module.
READY
START
ABB
1
Figure 4.1.9.1-1 Front connector (1) for remote communication
Via the optical PC-connector on the front panel the relay is connected to a PC used
for setting. The front interface uses SPA-bus protocol.
The optical PC-connector isolates the PC from the relay galvanically. The connection
consists of a transmitter stage and a receiver stage. The front connector is
standardized for ABB relay products and requires a specific opto-cable (ABB art. no
1MKC950001-1). The cable is connected to the serial RS-232C port of the PC. The
optical stage of the cable is powered by RS-232C control signals. The cable works
correctly with baud rates 4.8 and 9.6 kbps.
The following serial communication parameters shall be used for RS-232C:
• Number of data bits
• Number of stop bits
• Parity
• Baud rate
Relay data, such as events, setting values, all input and recorded data, can be read via
the optical PC-interface.
When setting values are altered via the optical PC-interface, the relay checks that the
entered parameter values are within the permitted setting range. The relay refuses to
accept too high or too low a setting value and keeps the former setting unchanged.
TRIP
C
E
7
1
even
9.6 kbps as default
ABB Substation Automation
Products and Systems
MRS750940-MUM