ABB REJ 523 Technical Reference Manual page 26

Overcurrent relay
Table of Contents

Advertisement

REJ 523
26
Technical Reference Manual
Table 4.1.3.3-3 SGF2
Switch
Function
SGF2/1
Automatic doubling of the start current of stage I>>.
When the switch is in position 1, the set value for the
stage is automatically doubled at start-up.
SGF2/2
Inverse-time operation of stage I> inhibited by the starting
of stage I>>.
When the switch is in position 1, the inverse-time
operation is inhibited.
SGF2/3
Inhibition of the operation of stage I>>.
When the switch is in position 1, the operation of stage
I>> is inhibited.
SGF2/4
Operation mode of the start indicator of stage I>.
When the switch is in position 0, the start indicator
automatically resets once the fault disappears.
SGF2/5
Operation mode of the start indicator of stage I>>.
When the switch is in position 0, the start indicator
automatically resets once the fault disappears.
SGF2/6
Not in use.
SGF2/7
Not in use.
SGF2/8
Not in use.
Σ SGF2
ABB Substation Automation
Products and Systems
Default
setting
0
0
0
0
0
0
0
0
0
MRS750940-MUM