ABB REJ 523 Technical Reference Manual page 41

Overcurrent relay
Table of Contents

Advertisement

ABB Substation Automation
Products and Systems
1MRS750940-MUM
Technical Reference Manual
Table 4.1.9.3-2 Parameters V1...V4
Recorded data
Number of starts of
stage I>
Number of starts of
stage I>>
Stage/phase that caused
operation
Operation indication code
The last five recorded values can be read with parameters V11...V97. Event n denotes
the latest recorded value, n-1 the next one, and so forth.
Table 4.1.9.3-3 Recorded data
Recorded data
Phase current I
L1
Phase current I
L2
Phase current I
L3
Start duration,
stage I>
Start duration,
stage I>>
Time stamp of
registered value, date
Time stamp of
registered value, time
Para-
R/W
meter
V1
R
V2
R
V3
R
V4
R
Event (R)
n
n-1
n-2
V11
V31
V51
V12
V32
V52
V13
V33
V53
V14
V34
V54
V15
V35
V55
V16
V36
V56
V17
V37
V57
REJ 523
Value
0...255
0...255
1=I
>
L3
2=I
>
L2
4=I
>
L1
8=I
>>
L3
16=I
>>
L2
32=I
>>
L1
0=no operation
1=starting of stage I>
2=tripping of stage I>
3=starting of stage I>>
4=tripping of stage I>>
5=tripping of CBFP unit
Value
n-3
n-4
V71
V91
0...50 x I
V72
V92
0...50 x I
V73
V93
0...50 x I
V74
V94
0...100 %
V75
V95
0...100 %
V76
V96
YY-MM-DD
V77
V97
HH.MM; SS.ms
n
n
n
41

Advertisement

Table of Contents
loading