ABB REJ 523 Technical Reference Manual page 40

Overcurrent relay
Table of Contents

Advertisement

REJ 523
40
Technical Reference Manual
Settings
Table 4.1.9.3-1 Settings
Variable
Start current of stage I>
Operate time or time
multiplier k of stage I>
Start current of stage I>>
Operate time of stage I>>
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGB 1
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Operate time of circuit-
breaker failure protection
Time setting for disabling
new trip indication on
LCD
1)
Values above 1 equal 1.
2)
If the protection stage has been set out of function, the number indicating the
currently used value is displaced by "999" in serial communication and by dashes on
the LCD.
Recorded data
Parameters V1 and V2 indicate the number of starts of the protection stages,
parameter V3 indicates the stage that has caused operation and parameter V4 the
operation.
Actual
Group 1
settings
(R, W, P)
(R)
S1
S41
S2
S42
2)
S3
S43
S4
S44
S5
S45
S6
S46
S7
S47
S8
S48
S9
S49
S10
S50
S11
S51
S12
S52
-
S121
-
S122
ABB Substation Automation
Products and Systems
Group 2
Setting
(R, W, P)
range
S81
0.30...5.00 x I
S82
0.05 ...300 s /
0.05...1.00
S83
0.30...35.0 x I
S84
0.04...300 s
S85
0...255
S86
0...255
S87
0...255
S88
0...255
S89
0...255
S90
0...255
S91
0...255
S92
0...255
S121
0.10...1.00 s
S122
0...999 min
MRS750940-MUM
n
1)
n