REJ 523
28
Technical Reference Manual
SGB1
Table 4.1.3.3-5 SGB1 Resetting / blocking with BI
Switch
Function
SGB1/1
SGB1/1 = 0: indicators are not reset by the binary input
signal.
SGB1/1 = 1: indicators are reset by the binary input
signal.
SGB1/2
SGB1/2 = 0: indicators and output contacts are not reset
by the binary input signal.
SGB1/2 = 1: indicators and output contacts are reset by
the binary input signal.
SGB1/3
SGB1/3 = 0: indicators, output contacts and memorized
values are not reset by the binary input signal.
SGB1/3 = 1: indicators, output contacts and memorized
values are reset by the binary input signal.
SGB1/4
Switching between the setting groups 1 and 2, either via
the serial bus with command V150, or using the external
binary input.
When SGB1/4=0, the setting group cannot be changed
with an external binary input.
When SGB1/4=1, the currently used setting group is
determined exclusively by the state of the binary input.
Note!
When SGB1/4 is set to 1, it is important that the switch
has the same setting in both the groups.
SGB1/5
Blocking of stage I> by binary input.
SGB1/6
Blocking of stage I>> by binary input.
When SGB1/5...6 = 1, tripping of the concerned stage is
blocked by an external binary input signal.
SGB1/7
Not in use.
SGB1/8
Not in use.
Σ SGB1
ABB Substation Automation
Products and Systems
Default
setting
0
0
0
0
0
0
0
0
0
MRS750940-MUM