46
Technical Reference Manual
Description
Internal fault code
SPA address of the relay
Data transfer rate, kbps
Rear communication
Relay serial number
CPU serial number
Hardware number
Test date
Software number
Software revision
Date reading and setting
(RED 500 format)
Time reading and setting
(RED 500 format)
Reading of event register
Re-reading of event
register
Type designation of the
module
Reading of module state
data
Resetting of module state
data
Time reading and setting
Date and time reading and
setting
Para-
R/W
meter
V169
R
V200
R, W
V201
R, W
V202
W
V230
R
V231
R
V232
R
V233
R
V234
R
V235
R
V250
R, W
V251
R, W
L
R
B
R
F
R
C
R
C
W
T
R, W
D
R, W
ABB Substation Automation
Products and Systems
Value
0...255
1...254
4.8 or 9.6
1=communication to rear
connector
ERxxxxxx
MRxxxxxx
1MRS090414-BAA
YYYYMMDD
1MRS118012
A...Z
YY-MM-DD
HH.MM; SS.mss
Time, channel number and
event code
Time, channel number and
event code
REJ 523
0=normal state
1=module been subject to
automatic reset
2=overflow of event
register
3=both events 1 and 2
0=resetting
1=reset only E50
2=reset only E51
4=reset all events including
E51, but not E50
00.000... 59.999 s
YY-MM-DD
HH.MM;SS.ms
MRS750940-MUM