Section 2
DNP3 data mappings
2.3.5.3
Table 18:
LD0.VMMXU1 Three-phase voltage limit supervision
IEC 61850 name
LD0.VMMXU1
.HiAlm.stVal
.HiWrn.stVal
.LoAlm.stVal
.LoWrn.stVal
2.3.5.4
Table 19:
LD0.RESVMMXU1 Residual voltage limit supervision
IEC 61850 name
LD0.RESVMMXU1
.HiAlm.stVal
.HiWrn.stVal
2.3.6
2.3.6.1
Table 20:
LD0.LEDPTRC1 Global protection signals
IEC 61850 name
LD0.LEDPTRC1
.Op.general
.Op.phsA
.Op.phsB
.Op.phsC
.Str.general
.Str.phsA
.Str.phsB
.Str.phsC
2.3.6.2
Table 21:
LD0.TRPPTRC1 Global conditioning (1)
IEC 61850 name
LD0.TRPPTRC1
.Op.general
.Tr.general
20
LD0.VMMXU1 Three-phase voltage limit supervision
SA name
HIGH_ALARM
HIGH_WARN
LOW_ALARM
LOW_WARN
LD0.RESVMMXU1 Residual voltage limit supervision
SA name
HIGH_ALARM
HIGH_WARN
Protection functions
LD0.LEDPTRC1 Global protection signals
SA name
-
-
-
-
-
-
-
-
LD0.TRPPTRC1 Global conditioning (1)
SA name
-
-
Description
High alarm
High warning
Low alarm
Low warning
Description
High alarm
High warning
Description
Global protection signals
-General Operate
-phsA Operate
-phsB Operate
-phsC Operate
-General Start
-phsA Start
-phsB Start
-phsC Start
Description
Operate input signal
Trip output signal
1MRS757056 C
Values
1=Alarm
1=Warning
1=Alarm
1=Warning
Values
1=Alarm
1=Warning
Values
1=Operate
1=Operate
1=Operate
1=Operate
1=Start
1=Start
1=Start
1=Start
Values
1=Operate
1=Trip
REU615
Point List Manual