Section 2
DNP3 data mappings
2.3.3.2
Table 11:
LD0.ARCSARC2 Fault arc protection stage 2
IEC 61850 name
LD0.ARCSARC21
.FADet.stVal
LD0.ARCPTRC21
.Op.general
2.3.3.3
Table 12:
LD0.ARCSARC3 Fault arc protection stage 3
IEC 61850 name
LD0.ARCSARC31
.FADet.stVal
LD0.ARCPTRC31
.Op.general
2.3.3.4
Table 13:
LD0.TCSSCBR1 Trip circuit supervision (1)
IEC 61850 name
LD0.TCSSCBR1
.CirAlm.stVal
2.3.3.5
Table 14:
LD0.TCSSCBR2 Trip circuit supervision (2)
IEC 61850 name
LD0.TCSSCBR2
.CirAlm.stVal
18
LD0.ARCSARC2 Fault arc protection stage 2
SA name
ARC_FLT_DET
OPERATE
LD0.ARCSARC3 Fault arc protection stage 3
SA name
ARC_FLT_DET
OPERATE
LD0.TCSSCBR1 Trip circuit supervision (1)
SA name
ALARM
LD0.TCSSCBR2 Trip circuit supervision (2)
SA name
ALARM
Description
Arc detected
Operate
Description
Arc detected
Operate
Description
Supervision alarm
Description
Supervision alarm
1MRS757056 C
Values
1=Detected
1=Operate
Values
1=Detected
1=Operate
Values
1=Alarm
Values
1=Alarm
REU615
Point List Manual