Ctrl.dxxxxx2 Controllable Disconnector (2); Ctrl.exxxxx1 Controllable Earth Switch (1); Sensors And Monitoring Functions; Ld0.Arcsarc1 Fault Arc Protection Stage 1 - ABB Relion REU 615 Manual

Hide thumbs Also See for Relion REU 615:
Table of Contents

Advertisement

1MRS757056 C
2.3.2.3
Table 8:

CTRL.Dxxxxx2 Controllable disconnector (2)

IEC 61850 name
CTRL.DCCILO2
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.DCCSWI2
.Pos.stSeld
CTRL.DCXSWI2
.BlkCls.stVal
.BlkOpn.stVal
2.3.2.4
Table 9:

CTRL.Exxxxx1 Controllable earth switch (1)

IEC 61850 name
CTRL.ESCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.ESCSWI1
.Pos.stSeld
CTRL.ESXSWI1
.BlkCls.stVal
.BlkOpn.stVal
2.3.3
2.3.3.1
Table 10:

LD0.ARCSARC1 Fault arc protection stage 1

IEC 61850 name
LD0.ARCSARC11
.FADet.stVal
LD0.ARCPTRC11
.Op.general
REU615
Point List Manual
CTRL.Dxxxxx2 Controllable disconnector (2)
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
CTRL.Exxxxx1 Controllable earth switch (1)
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN

Sensors and monitoring functions

LD0.ARCSARC1 Fault arc protection stage 1
SA name
ARC_FLT_DET
OPERATE
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Description
Arc detected
Operate
Section 2
DNP3 data mappings
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
Values
1=Detected
1=Operate
17