Section 2
DNP3 data mappings
2.3.1.2
Table 5:
LD0.LLN0 Settings supervision
IEC 61850 name
LD0.LLN0
.SetChg.stVal
.SetSeld.stVal
2.3.2
2.3.2.1
Table 6:
CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
IEC 61850 name
CTRL.CBCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.CBCSWI1
.Pos.stSeld
CTRL.CBXCBR1
.BlkCls.stVal
.BlkOpn.stVal
CTRL.CCBRBRF1
.OpEx.general
.OpIn.general
.Str.general
2.3.2.2
Table 7:
CTRL.Dxxxxx1 Controllable disconnector (1)
IEC 61850 name
CTRL.DCCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.DCCSWI1
.Pos.stSeld
CTRL.DCXSWI1
.BlkCls.stVal
.BlkOpn.stVal
16
LD0.LLN0 Settings supervision
SA name
-
-
Switchgear functions
CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
TRBU
TRRET
CB_FAULT_AL
CTRL.Dxxxxx1 Controllable disconnector (1)
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
Description
Settings changed
Settings reserved
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Failure ext.trip
Operate, re-trip
Start, timer running
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
1MRS757056 C
Values
1=Changed
1=Reserved
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
1=Failure
1=Operate
1=Start
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
REU615
Point List Manual