7.0 ANALOG (TRANSDUCER) OUTPUT OPTION

7.1 Introduction

The Transducer Output options (0 -1 mA or 4-20 mA) feature 3 separate outputs each
with two terminals, one of which is common to all three outputs and one which
provides a unique return path for each output.

7.2 Specifications

Outputs:
3 bi-directional,
0 – 1mA Current Range
Output Range:
Resolution:
Output Resistance: 500 ohm
4 – 20mA Current Range
Output Range:
Resolution:
Max Loop Voltage:
Max Voltage Drop:
4 – 20mA Internal Loop Supply
Max Output Voltage:
Accuracy
Data Update Rate (poll rate):

7.3 Connections

The connections for the 0-1mA output option are shown in figure 9, while the
connections for the 4-20 mA with external and internal loop are shown in figure 10.
ML0038
September 27, 2017
0-1mA (active) or 4-20mA (loop powered, passive)
0 to +/-1mA into 10K ohms or less; Overload to
+/-2.1mA into 5K ohms or less.
0.22uA
4 to 20mA
1.1uA
40Vdc
2.3V @ 20mA
6V @ 60mA,
0.25% of Full Scale Input
100ms minimum
- 65 -
Copyright 2017 Bitronics, LLC