Bitronics M350 User Manual page 14

3-phase ammeters & voltmeters
Table of Contents

Advertisement

Accuracy
Accuracies are specified at nominal Frequency and 25C, (unless otherwise noted). Unless noted, all values are true RMS
and include Harmonics to the 63rd (minimum).
Voltage
Current
Communication Ports
Serial (option*)
RS-232, RS-485, Software configurable ports
Baud rate: 9600 bps to 115.2 kbps
Ethernet
Single port; copper 10/100 Base-TX (standard)
Single port; LC fiber 100 Base-FX (option)
Analog Transducer
Refer to section 7.0 for specifications
Outputs (option*)
*Either the serial port or analog output may be ordered as an option, but not both
ML0038
AC: Better than 0.1% of reading (20 to 150 V rms, input-to-case).
(+/- 25ppm/DegC)
Input option 1
Better than 0.1% of reading +/- 20uA (>0.1A to 2.0A, -20C to 70C)
(Internal Isolation -
Better than 0.1% of reading +/- 50uA (0.01A to 0.1A, -20C to 70C)
1A ac)
Minimum reading 1mA
Input option 5
Better than 0.1% of reading +/- 100uA (>0.5A to 10.0A, -20C to
(Internal Isolation -
70C)
5A ac)
Better than 0.1% of reading +/- 250uA (0.05A to 0.5A, -20C to 70C)
Minimum reading 5mA
September 27, 2017
- 14 -
Copyright 2017 Bitronics, LLC

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the M350 and is the answer not in the manual?

Table of Contents

Save PDF