Terminal Strip

Check the terminal connections for firm seating and the terminals for damage.
6.4.10

Anti-Condensation Heaters

Check the effectiveness of the anti-condensation heating and the function of the existing monitoring device if
applicable.
6.4.11

Function Checks

6.4.11.1 Functional Check, Trip Circuits
Check the tripping action of the circuit-breaker via all the existing tripping paths.
6.4.11.2 Functional Check Lock-Out
6.4.11.2.1
Functional Check, Reclosing Lock-Out
During the process of charging the closing spring, the effectiveness of the reclosing lock-out must be checked by
means of an electrical CLOSE command. The tripping coil must not operate.
Perform this check at all poles.
6.4.11.2.2 Functional Check SF
At a level below the operating pressure, check the signal and the effectiveness of the function lockout SF
by means of electrical CLOSE and OPEN commands in all tripping paths. The circuit-breaker must not operate.
Lockout