SECTION 5 - PROGRAMMING THE IQ DP-4000

5.1 INTRODUCTION

This section identifies all of the programmable functions
of the IQ DP-4000. The device is programmed by
specifying setpoint values for functions you want
monitored. Setpoints are entered using the Save button
(S1), Setpoint Switches (S2), Rotary Select Switch (S3),
and are displayed via the Setpoint Display LED Bank
(DS30) (see Figure 2.2). Set the Rotary Select Switch
(S3) to 0 when you are finished programming.
Rotary
Select
Switch
Pressing & Holding S1 causes all 8 switches on S2 to be saved according to the Rotary Switch S3
(S3)
Always set all 8 S2 switches. See the pushbutton locations in Figure 2.2 (p.4).
S2.1
S3.0
System
S3.1
Configuration
S3.2
S3.3
S3.4
Phase Sequence
Reset Energy
S3.5
S3.6
Alarm 1
Relay Mode
S3.7
Alarm 2
Relay Mode
Alarm 1
S3.8
Disable/Enable
Alarm 1
S3.9
Overvoltage Detection
Alarm 2
S3.A
Disable/Enable
Alarm 2
S3.B
Overvoltage Detection
S3.C
Pulse Initiator
S3.D
Load Shed
S3.E
S3.F
Table 5.A Setpoint Master Sheet (The Most Important Page in This Manual)
S2.2
S2.3
Test Position—When you are not programming the unit, turn the Rotary Select Switch to 0.
Frequency
Power
Demand
Fixed/Sliding
Energy
Resolution
Alarm 1
Alarm 1
Latch/Unlatch
Overvoltage
Alarm 2
Alarm 2
Latch/Unlatch
Overvoltage
Alarm 1
Trip Delay
Alarm 2
Trip Delay
Alarm 1
Reset Threshold
Pulse Initiator
Parameter
Load Shed
Parameter
You use the Setpoint switches (S2) in conjunction with
the Rotary Select switch (S3) to program setpoint
values specific to your needs. Table 5.A, Setpoint
Master Record Sheet, lists all of the possible functions
that may be set. The left column lists the 16 Rotary
Select Switch Positions and the top row lists the
Setpoint Switches. Appendix B contains a blank Master
Setpoint Record Sheet for recording your setpoint
values. Use the details in this section to define your
setpoint values and record the values in the blank
Setpoint Switches (S2)
S2.4
S2.5
Nominal AC Line Voltage
Voltage Transformer Ratio
Current Transformer Primary
Power Demand
Time Interval
Not Used
Alarm 1
Alarm 1
Voltage
Undervoltage
Phase Loss
Alarm 2
Alarm 2
Voltage
Undervoltage
Phase Loss
Alarm 1
Undervoltage Detection
Alarm 2
Undervoltage Detection
Alarm 2
Reset Threshold
Load Shed /Restore Load
Range
TD 17548B
S2.6
S2.7
Voltage
Transformer
Ratio
Current Demand
Time Interval
Var/Power
Discrete
Factor Sign
Input
Alarm 1
Alarm 1
Voltage
Voltage
Phase
Phase
Unbalance
Reversal
Alarm 2
Alarm 2
Voltage
Voltage
Phase
Phase
Unbalance
Reversal
Alarm 1
Reset Delay
Alarm 1
Voltage Phase Unbalance Detection
Alarm 2
Reset Delay
Alarm 2
Voltage Phase Unbalance Detection
PowerNet
Programming
Load Shed /Restore Load
Range Settings
Pulse Initiator
Rate
S2.8
Current
Transformer
Primary
Sync Pulse
Alarm 1
Current
Phase Loss
Alarm 2
Current
Phase Loss
Alarm 1
Overvoltage
Detection
Alarm 2
Overvoltage
Detection
DP-4000 /
DP - 2 Mode
21