Bryant LEGACY 558J Product Data page 24

Single package rooftop cooling unit 3 to 6 nominal tons
Table of Contents

Advertisement

Table 12 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)
CFM
Vertical Economizer
Horizontal Economizer
CFM
1 Electric Heater Module
2 Electric Heater Modules
General fan performance notes:
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories
may add static pressure losses, as shown in Table 12. Selection software is available, through your salesperson, to help
you select the best motor/drive combination for your application.
4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would
work, Bryant recommended the lower horsepower option.
5. For information on the electrical properties of Bryant's motors, please see the Electrical information section of this
book.
6. For more information on the performance limits of Bryant's motors, see the application data section of this book.
600
800
1000
1250
0.01
0.02
0.035
0.045
---
---
---
---
600
900
1200
0.03
0.05
0.07
0.14
0.15
0.16
1500
1750
2000
0.065
0.08
0.12
---
0.1
0.125
1400
1600
1800
0.09
0.09
0.1
0.16
0.16
0.17
24
2250
2500
2750
0.145
0.175
0.22
0.15
0.18
0.225
2000
2200
2400
0.11
0.11
0.12
0.17
0.17
0.18
3000
0.255
0.275
2600
0.13
0.18

Hide quick links: