OPERATION AND
MAINTENANCE INSTRUCTIONS
GALAXY™
TWIN FANS

STORAGE / INSTALLATION

The unit must be stored in clean, dry conditions. DO NOT install these fans in areas where
the following may be present:-
1) Excessive oil or grease laden atmosphere.
2) Corrosive or flammable gases, fluids or vapours.
3) Ambient temperatures higher than 40
4) Relative humidity above 95%
5) Possible obstructions which will hinder removal.
6) Sudden ductwork transformations close to the unit.
If the unit is to be stored for a long period of time the fan impeller must be rotated by hand at
monthly intervals to prevent hardening of the lubricant and corrosion or static indentation of
the bearings.
It is recommended that before installation the resistance to earth should be measured and if
found to be less than 2 MΩ the motor should be dried out before applying mains voltage.

IMPORTANT - SAFETY

All air moving equipment may present electrical, mechanical or noise hazards either during
installation or during operation. These instructions are meant to help in the prevention and / or
minimisation of these hazards. It is important that due consideration is given to the
implementation of these instructions and to due attention being given to applicable statutory
requirements.
Potential hazards from rotating parts that can be reached during operation must be eliminated
by using appropriate guards meeting statutory requirements.
All electrical installation must be undertaken by a suitably qualified and competent person and
must be carried out in accordance with all relevant Statutory Requirements. Please check the
details on the unit rating plate to ensure that the correct power supply (Voltage, Frequency,
and Phase) is available. Do not use the fans with an incorrect power supply, overheating and
failure of the motor will occur.
All fans generate noise during operation. Dependant on the installation sound attenuators or
other acoustic treatment may be necessary to achieve acceptable noise levels in the
ventilated area or the area surrounding the fan installation. The product catalogues indicate
the noise levels generated by the equipment in standard test situations. The installed
condition may affect the actual noise levels experienced in operation.
Please note a wide range of accessories for this product are available from Vent Axia
Incorporating Roof Units Limited.
West Sussex. RH10 9YX.
o
o
C and below -15
C.
Fleming Way, Crawley,
Tel: 01293 526062
Fax: 01293 551188

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GALAXY GDD Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Vent-Axia GALAXY GDD Series

  • Page 1 OPERATION AND MAINTENANCE INSTRUCTIONS GALAXY™ Fleming Way, Crawley, West Sussex. RH10 9YX. TWIN FANS Tel: 01293 526062 Fax: 01293 551188 • STORAGE / INSTALLATION The unit must be stored in clean, dry conditions. DO NOT install these fans in areas where the following may be present:- 1) Excessive oil or grease laden atmosphere.
  • Page 2 • MOUNTING Galaxy belt and roof mounted direct drive fan units, must only be installed horizontally. The lid of the roof mounting unit should be removed to gain access to fit M10 coach screws (not supplied by Vent Axia Incorporating Roof Units Limited), when curb mounting. The optional mounting brackets (2 off brackets per unit) are recommended, when mounting the duct mounted units (GDD &...
  • Page 3 8) Check that the current (amps) taken by the fan does not exceed the current shown on the rating plate. 9) Ensure rotation of impeller is correct. Incorrect rotation may cause irreversible damage to the motor. Three phase units require a trial connection, to reverse direction interchange any two supply leads.
  • Page 4 Method For Checking Belt Tension Using a belt tension indicator, with metric calibration:- 1) Multiply the centre distance (in metres) by 16, this gives the deflection distance in mm. 2) Set the lower marking ring to the deflection distance required in mm on the lower scale. 3) Set the upper marker ring against the bottom edge of the top tube.
  • Page 7 Vent Axia Incorporating Roof Units Limited Guarantee Applicable only to products installed and used in the United Kingdom. For details of guarantee outside the United Kingdom, contact your local supplier. Vent Axia Incorporating Roof Units Limited guarantees its products for one year from the date of purchase against faulty material or workmanship.

Table of Contents