◆Introduction /Request, Warranty Period, and Notices Thank you for your purchase of LE5 series hybrid recorder having a 250mm recording width. Please read this instruction manual without fail for correctly and safely operating this unit and also preventing troubles in advance. Separate instruction manual This manual covers the operation of standard specifications and connection methods of a part of options.
Page 4
Cautions for safe use Observe the following cautions for using this unit safely. 1. Mounting place and terminal cover ① Panel mount type This unit is designed to be mounted on an indoor instrumentation panel. For using this unit, mount it on the panel without fail.
Page 6
8. Setting and changes by key operation 9. Adjustment function 8-1 Basic rules ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9-1 Zero and span adjustment of analog 1. Setting items and setting parameters ・・・・・・・ recording ・・・・・・・・・・・・・・・・・・・・・・・・・・・ 2 . Calling of setting items ・・・・・・・・・・・・・・・・・・・ 9-2 Zero and span adjustment of measured 3.
1. Introduction 1-1 LE5100/LE5200 1-4 Check and confirmation This hybrid recorder having a 250mm chart measures Check the unit for the following items before and records temperature (thermocouple, resistance operating it. thermometer bulb) inputs, DC voltage (mV, V) inputs, 1-4-1 Appearance check and other various industrial variables.
1-4-3 Type code No. check The operation may change according to the types. Confirm the type of your unit. Type table ■ LE5□□□-□□□ Model 1: LE5100 2: LE5200 No. of input points (analog inputs) 0: None 1: 12 points 2: 24 points 3:...
1-5 Major functions This unit provides various functions. For details of setting and operation, refer to each item No. Functions Items Contents Page No. Measuring data in each channel are displayed. Channel No. (3 digits) + tag (8 digits) + range (3 digits) + measured value (7 digits) An 8-digit tag can be set and displayed.
Page 10
Functions Page No. Items Contents ① Year, month, day, - Year, month, day, and time (time line) are printed at a designated interval. and time printing 1) A list of all parameters is printed at a requested time. Page 8-20 ②...
Red LED flickers in the occurrence of an alarm. ・PC.CARD Green LED remains lit when PC card is being inserted. ・REC.ON Green LED lights when recording is turned on. Recording is turned on or off by REC key. ・CHINO CHINO brand lights when power is turned on.
Page 12
Indications of the display section Measuring data display □□□ □□□ □□□□□□□ □□□□□□□□ :1Measuring data display by 1 channel Channel display: 3 digits Range display: 3 digits Measuring data display 7 digits Tag No. display: 8 digits or Digits unit display 8 5-digit display in case of collective ※...
2-4 Keyboard Names and functions of keys Names of keys Functions Enter key Enters various setting. Escape key Returns the screen to the last one each time this key is pressed once. Menu key Displays various setting items. Up-Down, These keys are used to shift the cursor upward, downward, leftward, or Left-Right keys rightward.
3. Mounting method This unit can be used on a desk or the like, but it is constructed to be used by mounting it on a panel (instrument panel). 3-1 Selection of mounting place 3-1-1 Ambient temperature and humidity 3-1-3 Mounting angle Temperature range : 0 to 40℃...
4. Connections Cautions on connections 1. Feed source power supply ● An electromagnetic switch or the like ● For feeding power to the unit, use a single-phase power Major generation ● A power line having waveform distortion source having the stable voltage without any distorted sources ●...
4-3 Connections of each terminal board 4-3-1 Measuring input terminal board CH1 oltage Thermo- couple Resistance Terminal cover mounting screw bulb thermometer (at 2 upper and lower places) Contact CH12 Cautions 1. Connect a voltage lower than the allowable input voltage to the input terminals. ①...
4-3-3 Communication I/F terminals, contact output terminals, and external drive terminals Output relay terminals Contact capacity 100V-240V AC 3V resistive load Terminal cover Setting of alarm output and fail output such as chart end and equipment abnormality are available from output relay terminal. Fail output is outputted in spite of not setting, but in the case of outputting of alarm, refer to 8-6 [Alarm setting], and set...
3. Output relay terminal connections Cautions 1. Connect a load of less than the designated contact Buffer relay capacity to the output relay terminals. This unit 2. Turn off the feed power source and buffer relay a b power supply before starting connections for N.O...
5. Installation of auxiliary products 5-1 Mounting method of chart (Caution) Pay attention to the injury related to dropping of the chart cassette after pulling it out of the internal unit. For inserting it to the internal unit, pay attention not to put your fingers caught by the unit. ①...
5-2 Ribbon cassette mounting method ① Prepare the ribbon cassette. Loosen the ribbon cassette ④ Keep the printer carriage unmovable by pressing it with about 10mm by pressing it in the arrow direction using the the left hand, and mount the ribbon cassette in the arrow shaft of a ball-point pen or the like.
6. Operation 6-1 Turning on the power supply 1) Confirm the connections. 2) After opening the door, turn on the power switch at the upper right of the chassis. Power ON <Display> <Printer> — LE Series — Initial position detection After about 5 seconds, Date, time, chart speed, and [POWER ON ***] data are displayed.
6-3 Recording operation 1) Recording ON-OFF Recording can be turned on and off by Rec key and Enter key. ① By pressing Rec key under Rec. ON condition, a message [Do Start you terminate chart recording?] is displayed on the display unit. By pressing Rec key under Rec.
7. Initial setting at the delivery time from the factory 7-1 Setting items at the delivery time from the factory Items Initial setting items (1) Time Present time (year, month, day, Japanese time) (2) Range Models LE5100/LE5200 Item ① Input type V(-10.000...
7-2 Mode change by soft switch The LE5000 series is able to select ON/OFF (show/not show) of various printing by initial settings. Refer to below for setting as required. Initial setting in factory delivery is all [ON]. 1. Indication method of setting screen When turn on the power supply of instrument, [LE Series] is displayed in the display screen.
8. Setting and changes by key operation 8-1 Basic rules Read these rules without fail before starting setting This paragraph describes general common items in setting operation. 1. Setting items and setting parameters In measurement and recording, versatile recording results and data are obtained according to various conditions setting of this unit.
Page 26
1. Confirmation method in case of one setting parameter ① Select the setting display mode by pressing Menu key. Start A window opens to display a list of setting items. ② Move the cursor by ◄•►•▲•▼ keys and select an item to ①...
Page 27
2. Confirmation method in case of plural setting parameters ① Select the setting display mode by pressing Menu key. Start A window opens to display a list of setting items. ② Move the cursor by ◄•►•▲•▼ keys and select an item to ①...
7. Setting change For setting change, shift the cursor to a desired point to be changed. For moving the selection system parameters by cursor, ▲•▼ keys are used. However, ◄•► key is normally used. Setting can be changed by the substitution method, edition method by shifting the cursor, and new setting method after erasing all setting.
11. Basic entry of setting parameters When various setting parameters are entered, a window opens to display a setting parameter entry screen. The basic common operation in the setting parameter entry screen is as shown below. Example 1: Chart recording setting screen; In case of selection of setting parameters by ▲・▼ keys. 1.
Page 30
Example 2: Display mode setting screen; In case of inputting a setting parameter by using keys 1. When the setting parameter entry screen is displayed, AD ① is high-lighted. (The cursor is present on AD) By pressing Enter key under this condition, parameter input area ②...
8-2 Display setting This unit comprises 4 kinds of display modes. The present display mode is [12CH], but the other display mode is settable as occasion demands. ① Select the setting display mode by pressing Menu key. Start A window opens to display a setting items table. ②...
8-3 Channel parameter setting [CH PARAM.] Range, RJ (internal/external switching of reference junction temperature compensation), scale, unit, etc. of each channel can be set collectively every channel. ① Select the setting display mode by pressing Menu key. Start A window opens to display a setting items table. ②...
Page 33
⑩ By pressing Func1 in the screen display in ⑥ above, [Points] Channel parameter setting short-cut the following screen is displayed. Screens ⑥, ⑩ Items ①-⑥ on the last page can be short cut so long as are used for confirming the setting and copying the the channel parameter setting is concerned.
1.Operation recording Operating conditions of peripheral units or the like are recorded at an optional position of the chart as operation recording. This function is provided as a relative recording function between system conditions and measuring data. Max. 36 records can be marked on the chart. Communication Contact input Data display...
2.Data communication input The “data communication input” is the function that records and calculates the data concurrently with measuring data which is sent from the host via the communication interface. 【Setting method】 1)This operation is done by setting channel parameters. (Ⅰ. Instruction Manual 8-2 [CH. Param.]) 2)For input, select “COMM”.
8-4 Dot setting [DOT] Tags and dot colors can be set every channel. Ten dot colors can be set optionally every channel. ① Select the setting display mode by pressing Menu key. Start A window opens to display a setting items table. ②...
8-5 Chart recording setting [CHART] Chart speed and dotting cycle can be set. An optional cycle to be set here becomes a dotting cycle. In this case, the dotting synchronization must be set to [Optional cycle]. ① Select the setting display mode by pressing Menu key. Start A window opens to display a setting items table.
Page 38
(Caution 1) Dotting synchronization (dotting cycle) The [Chart speed] is dotted as analog recording every 0.2mm in the vertical (time axis) direction at all times. Since the printer dots data at a ratio of about 1 line/3 seconds, analog recording is intermittent, if recording is done at a chart speed of higher than 240mm/h [Optional cycle] means the dotting at a preset dotting cycle, and it is used when the input changes abruptly.
8-6 Alarm setting [ALARM] Alarm setting means the setting of a higher-limit or lower-limit alarm point at an optional point in the analog recording range. Number of alarm points can optionally be set up to 4 points per channel, and the kinds of alarms (higher-limit alarm or lower-limit alarm) can be set optionally.
Page 40
4. Alarm setting ① Select the setting display mode by pressing Menu key. Start A window opens to display a setting items table. ② Move the cursor by◄•►•▲•▼keys and select an item to be set. ③ Select ALARM. ① Menu key ④...
Page 41
5. Alarm check ⑩ By pressing Func1 in the screen display in ⑥ Whether an alarm occurred or not can be recognized in above, the following screen is displayed. Screens ⑥, ⑩ are used for confirming the normal data display screen. The kinds of alarms, level, etc.
C, while the other records a difference between ②D channel data and a reference value in channel E. (This function is provided in LE5100 only. In case of LE5200, this function is executed by the mathematical configuration.)
Page 43
Setting of channel parameters for operation output channel Refer to 8-3 Channel parameter setting, designate an output channel out of channels in and after CH037. Select a channel in and after CH037 and press Enter key. The following window opens to display the setting parameter entry screen. In this setting parameter entry screen, settable items are input, unit, lower-limit of chart recording, higher-limit of chart recording, tag, display skip, digital printing skip, and memory card recording skip only.
Page 44
① Select the setting display mode by pressing Menu key. A window opens to display a setting items table. Start ② Move the cursor by ◄•►•▲•▼keys and select an item to be set. ③ Select CALC. ④ Enter the setting table display (collective 12 points) screen by ①...
8-8 Message printing setting [MESSAGE] A simple message can be printed. Max. 75 characters can be set when a channel is designated or max. 80 characters can be designated when no channel is designated; provided that these characters are restricted to those on the keyboard.
8-9 List printing setting [LIST PRINT] This function is used for confirming the setting contents. List printing comprises all setting items list printing to print all setting items being set at present and designated items list printing to print designated setting items only. All items list printing List printing of all preset setting items List printing...
8-10 Data interval recording setting [DATA INT.] This unit digitally records measuring data of all channels at a desired time and a desired interval time. Interval time : Set a digital recording time interval (once every certain hours and certain minutes). (Max. 24 hours every minute step) Time and time setting Start time : Set the start time of digital recording (from certain hours and...
8-11 Logging recording setting [LOGGING] This unit digitally records measuring data of all channels at a desired time and a desired interval time. Analog recording is not done during logging recording. Interval time : Set a digital recording time interval (once every certain hours and certain minutes).
8-12 Data print recording setting [DATA PRINT] Two kinds of data print formats are prepared. Set them according to uses. ① Select the setting display mode by pressing Menu key. Start A window opens to display a setting items table. ②...
8-13 Display setting [DISPLAY] Kinds of display, update cycle, display brightness, and chart illumination setting can be done. ① Select the setting display mode by pressing Menu key. Start A window opens to display a setting items table. ② Move the cursor by ◄•►•▲•▼ keys and select an item to be set. ③...
8-14 Engineering port setting [ENG.] Various parameter settings in this instrument are changed and set by computer if [PASS], which is sold separately, is used. The computer and this instrument communicate by USB. In this case, setting USB address is necessary.
8-15 Date and time setting [DATE/TIME] This unit is provided with a built-in clock for indicating year, month, day, hour, and minute. The present time is set at the delivery time from the factory. The clock can be set to an optional time as occasion demands. ①...
8-16 System setting [SYSTEM 1] This unit provides a setting function about setting inhibition and permission system. By inputting the password, the inhibition of setting change, memory clear (delivery condition from factory), dotting positions (zero, span), and input correction enable/disable conditions can be operated. Use this function as recovery processing when this unit does not function normally due to wrong operation, etc.
Page 54
8-17 PC card (memory card) setting [PC CARD] 8-17-1 Summary Measuring data recorded by this unit can be stored into a PC card at an optional start time and a designated interval (highest speed 100sec). The measuring and recording conditions of the range, scale, chart speed, etc. can be entered into the PC card in advance, and the unit can be set up with the entered setting contents as occasion demands.
8-17-4 Handling of PC card 1. Cautions to be observed before use CAUTIONS ●The PC card as an accessory of this unit is a CF card with an ●Don’t use or store this product at a hot, wet or dusty place or a adapter mounted.
8-17-6 Setting of measuring data saving by PC card [DATA WR.] ①Select DATA WR. Start ②Press Enter key to select the parameter entry mode of an item to be set. A window opens and the setting parameter entry screen is displayed. (For the setting parameter entry screen, refer to ④) ①...
8-17-7 Setting of set value saving by PC card [PAR.SAVE] ①Select PAR. SAVE. ②Press Enter key to enter the parameter entry mode of a desired item Start to be set. A window opens and a save selection screen is displayed. ①...
8-17-8 Setting of reading out a set value by PC card (PAR. LOAD) ①Select PAR LOAD. Start ②Press Enter key to enter the parameter entry mode of a desired item to be set. A window opens and a setting parameter entry screen is displayed. ①...
8-17-9 PC card format [FORMAT] ①Select FORMAT. ②Press Enter key to enter the parameter entry mode of a desired item to Start be set. A window opens and a message is displayed to demand either ① FORMAT formatting or check. (For the setting parameter entry and check screen, refer to item ④) ③For stopping the setting, the screen returns to the last one, each time Enter key...
8-17-10 PC card removing [REMOVE] ①Select REMOVE. ②Press Enter key to enter the parameter entry mode of a desired item to Start be set. A window opens and a message is displayed to demand either ① REMOVE stopping operation or check. (For the setting parameter entry and check screen, refer to item ④) ③For stopping the setting, the screen returns to the last one, each time Enter key...
9. Adjustment function This unit provides 3 kinds of adjustment functions. Carry out necessary adjustment according to symptoms. These adjustments are processed by software without any trimmer or other mechanical means. Zero and span adjustment of analog recording ① Kinds of adjustment functions Zero and span adjustment of measured values ②...
9-2 Zero and span adjustment of measured values [INPUT ADJ.] Adjust zero and span if the accuracy is out of the specified value due to an surrounding environment, a secular change, or other causes as calibration results. This zero and span adjustment applies to data display and digital recording to the range setting every channel.
9-3 Shift adjustment of measured values This function is provided to adjust the shift (parallel move) quantity of data display and digital recording. This function is used for correcting the dispersion of sensors, an input converter, etc. This adjustment can be done every channel in two ways. 1.
9-4 Calibration Calibration is done every channel, in principle. Even if the same range is set, an error may occur between channels to be exact. Preparation ① Turn off the power switch and connect cables according to input signals. (See the following figure) Connect the input terminals of this unit to a channel to be calibrated.
10. Troubleshooting If this unit does not function normally, check it according to the following table. If the unit is still in trouble after checking it, contact your nearest sales agent or shop from which you bought your unit. Troubleshooting table Symptoms Check contents (1) The unit does not function at all even...
11. Maintenance and check ① Carry out the maintenance and check periodically to use the unit under normal conditions at all times. ② For the maintenance and check, observe the following table. Replace or supply consumables, and carry out lubrication as occasion demands. Maintenance and Processing methods check items...
11-1 Recommendable parts exchange cycles It is recommended for using the unit for a long time under normal conditions to replace parts periodically as preventive maintenance. Warning: Parts exchange Don’t replace any parts other than the chart and ribbon cassette as consumables, otherwise the unit cannot be restored normally, and also, a dangerous accident may occur.
12. General specifications No. of measuring points : 12 points, 24 points and 36 points in 3 kinds Kinds of inputs Full multi-range (TC, mV, Pt contact) : Thermocouple・・・ B, S, R, N, K, E, J, T, WRe5-WRe26, W-WRe26, PtRh40-PtRh20, NiMo-Ni, PlatinelⅡ, U, L DC voltage・・・・・・...
Page 69
Alarm printing : Generation or cancellation mark in tag (Channel number in case of non-setting), kinds of alarms, (when option is added) generation and cancellation time, level, and analog recording Scale printing : Minimum value, maximum value, tag (Channel number in case of non-setting) List printing :...
Page 70
International standard : Low voltage directive ・・・ EN61010-1, EN61010-2-30, Installation category ・・・ CAT.Ⅱ, Pollution (CE marking) degree 2 *Except for LE5300 EMC directive ・・・ EN61326-1 ClassA *Indication value equivalent to ±10%FS fluctuates during the test. RoHS directive ・・・ EN50581 *When it is high humidity in that condition of transportation and storage, readjustment will be needed. For detail of readjustment, refer to instruction manual 9-4.
Page 71
■Measuring ranges, accuracy rating, and display resolution Kinds of inputs Measuring ranges Reference range Accuracy rating Display function -10.0 to 10.0mV ±10mV 1μV -20.0 to 20.0mV ±20mV -40.0 to 40.0mV ±40mV 10μV -80.0 to 80.0mV ±80mV DC voltage ±0.05%±1digit -1.25 to 1.25V ±1.25V...
Page 72
K,E,J,T,R,S,B,N,: IEC584,JIS C1602-1995 W-WRe26,WRe5-WRe26,PtRh40-PtRh20,NiMo-Ni,PlatinelⅡ: ASTM Vol.14.03 U(Cu-CuNi),L(Fe-CuNi): DIN43710 Pt100 : IEC751,JIS C1604-1997 JPt100 : JIS C1604-1981,JIS C1606-1986 Exceptional standards of accuracy rating ■ Note) Each reference range conversion accuracy applies to thermocouple inputs. Kinds of inputs Measuring ranges Accuracy rating -200...
13. Option specifications Option names Option contents A 1/1000 voltage divider can be mounted externally every channel. As a result, inputs up to DC voltage 50V can be measured. Voltage division ratio : 1/1000 External mounting Voltage division accuracy : 0.1% of voltage divider ±...
13-1. External drive Chart speed can be selected and data can be printed by external contact signals (no-voltage contacts: short-circuit or open) without any setting keying operation. One of 3 chart speeds and stop can be selected. Three kinds of chart speed can be set optionally by keying operation of this unit, and also, the dotting synchronizing mode can be set every chart speed.
Page 75
〔Example: Chart speed selection by an alarm output〕 Set another alarm to a value which is more or less lower than the necessary alarm point, and switch the chart speed by its output. Thus, detail records of measuring data before and after the necessary alarm point can be obtained. Alarm setting Necessary alarm point:...
Page 76
【Setting method】 ①Press Menu key to enter the setting display mode. A window opens Start and a setting items table is displayed. ②Select a desired item to be set by moving the cursor by means of ・ ・▲・▼ keys. ① Menu key ③Select DIG.IN.
13-2. Alarm output Three kinds of alarm output points (12 points, 24 points, and 36 points) are prepared. Confirm the model code. For the alarms and setting and connections of alarm outputs, refer to [Ⅰ.Instruction Manual]. 1. Alarms and alarm output setting ------- 8-6 Alarm setting Setting and assignment of alarm output channels are as shown below.
13-3. Recording format The analog recording format can be changed by selecting one of the following records. Select them according to uses. ・AUTO RNG Recording ranges are selected automatically according to input sizes. - The analog recording range is partially compressed or expanded. ・COMP -...
13-3-1. Automatic range selection recording ・Recording ranges can be set up to max. 5 stages every channel. ・Each range is automatically selected to the next range when it exceeds zero or span of each stage by 0.5mm on the analog trace. ・The relation between range stage number and each span setting is No.1 zero <...
13-3-2. Partial compression and expansion recording ・This setting can be done every channel. ・Since maximum 2 dots can be set, maximum 3 compression or expansion ranges are obtained. ・Set the dot recording position by % and then, set an analog recording scale value at the dot (%). 【Setting method】* Set the following setting after checking if the [COMP.] is selected on analog recording format (p13-6).
13-3-3. Parallel scale recording ・The analog recording range is divided into maximum 5 areas and set values can be divided into groups and recorded. ・For the number of areas and each recording range, refer to the following figure. Both ends of each area are the minimum and maximum values of the range setting analog recording range.
13-4. Rate-of-change alarm/Differential alarm 13-4-1. Rate-of-change alarm ・When dt changes width (refer to below) and increases or decreases from the predicted measuring data, and is over the alarm setting value, alarm occurs. ・Rate-of-change alarm has two kinds of alarms, which are increase limit and decrease limit. Both limits alert when change width of dt is over the setting value.
13-4-2. Differential alarm ・When input difference (absolute value) of 2 channel is over the alarm setting value, alarm will occur. ・Differential alarm has differential higher-limit alarm and differential lower-limit alarm. In differential higher-limit, alarm occurs when difference of input is bigger then alarm setting value. In differential lower-limit, alarm occurs when difference of input is less then alarm setting value.
13-5. Operation Function of recording operation between several channel or operation results of time series of specific channel to specified channel. Data of operation of output channel is performed analog recording/digital recording/data display like data of general input intake, and also performed recording format/skip specified. 【Operation type】...
Page 85
2.Inter-channel 1)Refer to setting of differential recording and set it. (Ⅰ.Instruction manual 8-7.「CALC.」 ) 2)Select [MIN], [MAX], [AVE], or [SUM] for kind. 3)Refer to previous page [1. Differential operation] for screen of setting list display (collective 12 point) Unrelated items for type which is set in operation output channel is not displayed. 4)Refer to previous page [1.
Page 86
4. Operation formula 1) Refer to setting of differential recording and set it. (Ⅰ.Instruction manual 8-7.「CALC.」 ) 2)Select [EXT] for kind. 3)Refer to previous page [1. Differential operation] for screen of setting list display (collective 12 point) Unrelated items for type which is set in operation output channel is not display. 4)Refer to previous page [1.
Page 87
4-4-3. Logical operation The logical operation for 1 or 0 is performed and the result is returned as 1 or 0. Symbol Example Remarks Logical AND X AND Y Logical OR X OR Y Exclusive OR X XOR Y Negation NOT( X ) ※X and Y indicate the formula or the numeric value.
Page 88
2. 24-hour totalizing operation The totalized values are reset only at totalizer reset reference time. Entering method of the formula ITG24(d) d: Channel number to be totalized The calculation contents are same as the standard totalizing operation. 2) F-value Entering method of the formula FV(X#To#Z#R)...
Page 90
32-8, KUMANO-CHO, ITABASHI-KU, TOKYO 173-8632 Telephone : 81-3-3956-2171 Facsimile : 81-3-3956-0915 Printed in Japan (...