ibaMS8xIEPE
7.2.2

Status of IEPE inputs

LED per
channel
L26 ... L33
7.3

Analog inputs

Important note
A channel requires a settling time of about 10 to 50 seconds after switching on. The
settling time in IEPE 1 Hz mode is shorter than in IEPE 0.1 Hz mode.
This also applies, if the signal was overdriven for a short time.
The analog inputs can be adjusted to different operating modes per channel. The oper-
ating mode is configured in ibaPDA.
 IEPE input (±5 V) with 1 Hz high-pass filter
 IEPE input (±5 V) with 0.1 Hz high-pass filter
 24 V AC input (AI)
 24 V DC input (AI)
4 inputs are adjusted permanently to IEPE mode. The mode of the second input of each
root can be configured: IEPE, 24 V AC or 24 V DC. The following table shows the possi-
ble settings:
Analog input 0
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Analog input 5
Analog input 6
Analog input 7
Default setting
2
Manual
Status
IEPE mode
Off
Channel not active
Green
± (0 V ... 4.5 V)
0...90%
inside measuring range
Yellow
± (4.5 V ... 5.0 V)
90 ... 100%
out of measuring range
Red
Not connected or broken line
(Vcc > 20 V)
Shorted
Red
flashing
IEPE 1 Hz
IEPE 0.1 Hz AI-24 V AC
Issue 1.3
AI mode
± (0 V ... 0.3 V)
± (0.3 V... 21.6 V)
± (21.6 V ... 24 V)
Out of measuring range
2
-
-
-
-
AI-24 V DC
-
-
-
-
13