12.4.2 System Does Not Start

LED display output:
Description:
Possible causes:
Table 48
Procedure:
Figure 35
1)         I f high voltage power to the unit is interrupted and then restored, the compressor
ALWAYS waits at least 3 mins before it starts via a thermostat Y call, the outdoor
fan motor will always start immediately upon thermostat Y call.
2)  In cooling mode: There is at least a 6 minute delay between when the thermostat
is satisfi ed and compressor can turn back on with a Y call.
3)  In heating mode: There is at least a 3 minute delay between when the thermostat
is satisfi ed and compressor can turn back on with a Y call.
Bosch Thermotechnology Corp. | 07.2021
No fault code displayed
High voltage power is available to the unit, unit is given call for heating/cooling, system does not start
 The thermostat is improperly wired
 Thermostat not giving call for heating/cooling
 Damaged thermostat
 Disconnected compressor wiring harness
If your unit is not starting it may be
due to a designed delay. Check
Notes 1-3.
Check that thermostat is sending call
for heating/cooling
No
Is the wiring correct
according to wiring
diagram?
Yes
No
Is there 18-28VAC
and 0VDC between
Y&C and B&C at
the outdoor unit?
Yes
Yes
Is the compressor
wire disconnected?
Refer to Appendix 1
No
No
Is there 230VAC
power at high
voltage terminal?
Yes
Power off and wait at least 3
minutes before powering on
Correct wiring
Correct thermostat wire
connection/replace the
thermostat
Connect the compressor
wire
Correct power supply
Bosch IDS 2.0 | 61