Lennox INNOV DM R Series Application Manual page 84

Close control unit ec plug fan
Table of Contents

Advertisement

1.4
Hydraulic section (CW version)
3-way valve
The 3-way valve used on INNOV@DM CW version units for inlet water flow regulation allowing a foundamentally
maximum precision's regulation on CCAC applications.
Tab. 3
Technical characteristics
Brand / valve's type
3
Kvs valve (m
PN valve
DP max. (kPa)
Connections (inch)
All INNOV@DM CW units are supplied with 3-way valve setted by 3 points motor. Upon request, is possible to
set an advanced precision control with 0 ÷ 10 V signal regulation.
Air presence on hydraulic circuit
It is necessary to leak air from the hydraulic circuit of unit after the connection to the external circuit. To do this,
open the frontal panels and remove the air filter; after this, open the small valve on the right-top side of the coil's
collector (take the front side of unit in reference). Use adapted tools for the manual valve's setting.
Fig. 5
Basic cooling circuit (CW version)
4
M
5
Pos.
Description
1
Chilled water inlet
2
Chilled water outlet
3
3-way valve
4
Plug fan
INNOV@ CENT -AGU-0912-E
Frame 1
Controls VMT2
/h)
4
16
250
1/2"
2
1
3
6
Standard
Frame 2
Controls VMT2
4
16
250
1/2"
4
M
6
5
Opt. 2-way valve
Pos.
Description
5
Coil heat exchanger
6
Breather valve
7
2-way valve (Opt.)
-
Frame 3
Controls VMBT3
6.3
16
170
3/4"
2
1
7
. 8 .

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Innov dma r seriesInnov dmc r series

Table of Contents